Additional Information

Part Number
1032207
UPC
4055626536415
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Lightning current arrester for power supply systems
Class Code : EC000381
Version : 7

Dimensions

Height
223.2 mm
Width
47 mm
Width
52 mm (with spacer lid)
Depth
110.7 mm
Horizontal pitch
3 Div.

Connection data

Connection method
Screw connection
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
18 mm
Conductor cross section flexible
2.5 mm² - 35 mm²
Conductor cross section solid
2.5 mm² - 35 mm²

Ambient conditions

Degree of protection
IP30 (Installed)
Ambient temperature (operation)
-40 °C - 80 °C
Ambient temperature (storage/transport)
-40 °C - 80 °C
Altitude
≤ 6000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % - 95 %

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Protective circuit

Nominal voltage UN
230/400 V AC (TN-S)
Nominal voltage UN
230/400 V AC (TT)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
255 V AC
Residual current IPE
≤ 5 µA
Nominal discharge current In (8/20) µs (L-N)
20 kA
Nominal discharge current In (8/20) µs (L-PE)
20 kA
Nominal discharge current In (8/20) µs (N-PE)
80 kA
Impulse discharge current (10/350) µs (L-N), charge
6.25 As
Impulse discharge current (10/350) µs (L-N), specific energy
39 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp
12.5 kA
Impulse discharge current (10/350) µs (L-PE), charge
6.25 As
Impulse discharge current (10/350) µs (L-PE), specific energy
39 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp
12.5 kA
Impulse discharge current (10/350) µs (N-PE), charge
25 As
Impulse discharge current (10/350) µs (N-PE), specific energy
625 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp
50 kA
Follow current interrupt rating Ifi (L-N)
25 kA
Follow current interrupt rating Ifi (L-PE)
25 kA
Follow current interrupt rating Ifi (N-PE)
100 A
Short-circuit current rating ISCCR
25 kA
Voltage protection level Up (L-N)
≤ 1.5 kV
Voltage protection level Up (L-PE)
≤ 2 kV
Voltage protection level Up (N-PE)
≤ 1.5 kV
TOV behavior at UT (L-N)
337 V AC (5 s / withstand mode)
TOV behavior at UT (L-N)
442 V AC (120 min / safe failure mode)
TOV behavior at UT (L-PE)
442 V AC (120 min / withstand mode)
TOV behavior at UT (L-PE)
1455 V AC (200 ms / withstand mode)
TOV behavior at UT (N-PE)
1200 V AC (200 ms / withstand mode)
Response time tA
≤ 100 ns
Max. backup fuse with branch wiring
250 A (gG)

Standards and Regulations

Standards/regulations
IEC 61643-11 2011
Standards/regulations
EN 61643-11 2012