Type 2 surge arrester - VAL-MS 350 VF-RW/3+0-FM/40 - 1050284
1050284
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price

Additional Information

Part Number
1050284
UPC
4055626666501
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Surge protection device for power supply systems
Class Code : EC000941
Version : 7

Additional descriptions

Note
Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a).

Dimensions

Height
98.7 mm
Width
53.4 mm
Depth
65.7 mm (incl. DIN rail 7.5 mm)
Horizontal pitch
3 Div.

Connection data

Connection method
Screw connection
Screw thread
M5
Tightening torque
3 Nm (1.5 mm² - 16 mm²)
Tightening torque
4.5 Nm (25 mm² - 35 mm²)
Stripping length
16 mm
Conductor cross section flexible
1.5 mm² - 25 mm²
Conductor cross section solid
1.5 mm² - 35 mm²
Conductor cross section AWG
15 - 2
Connection method
Fork-type cable lug
Conductor cross section flexible
1.5 mm² - 16 mm²

Indicator/remote signaling

Switching function
PDT contact
Operating voltage
5 V AC - 250 V AC
Operating voltage
30 V DC
Operating current
5 mA AC - 1.5 A AC
Operating current
1 A DC
Connection method
Plug-in/screw connection via COMBICON
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section flexible
0.14 mm² - 1.5 mm²
Conductor cross section solid
0.14 mm² - 1.5 mm²
Conductor cross section AWG
28 - 16

Ambient conditions

Degree of protection
IP20 (only when all terminal points are used)
Ambient temperature (operation)
-40 °C - 80 °C
Ambient temperature (storage/transport)
-40 °C - 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % - 95 %
Shock (operation)
25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (10 - 500 Hz / 2.5 h / X, Y, Z)

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1

Protective circuit

Nominal voltage UN
240/415 V AC (TN-C)
Nominal voltage UN
230 V AC (IT)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
350 V AC
Rated load current IL
80 A
Residual current IPE
≤ 5 µA
Standby power consumption PC
≤ 6 mVA
Nominal discharge current In (8/20) µs
10 kA
Maximum discharge current Imax (8/20) µs
20 kA
Impulse discharge current (10/350) µs, charge
1.25 As
Impulse discharge current (10/350) µs, specific energy
1.56 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp
2.5 kA
Short-circuit current rating ISCCR
25 kA
Voltage protection level Up
≤ 1.5 kV
Residual voltage Ures
≤ 1.35 kV (at In)
Residual voltage Ures
≤ 1.35 kV (at 10 kA)
Residual voltage Ures
≤ 1.2 kV (at 5 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs
≤ 1.5 kV
TOV behavior at UT (L-PEN)
415 V AC (5 s / withstand mode)
TOV behavior at UT (L-PEN)
440 V AC (120 min / withstand mode)
Response time tA
≤ 100 ns
Max. backup fuse with V-type through wiring
80 A (gG)
Max. backup fuse with branch wiring
125 A (gG)

Standards and Regulations

Standards/regulations
IEC 61643-11 2011
Standards/regulations
EN 61643-11 2012

CAD Models

Trace parts
Trace parts
Download