Temperature measuring transducer - MACX MCR-TC-I-C - 1052459
1052459
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Input data

Input
Intrinsically safe
Sensor types that can be used (TC)
B, E, J, K, N, R, S, T, L, U, C, D, A-1, A-2, A-3, M, Lr
Temperature measuring range
-250 °C - 2500 °C (Range depending on the sensor type)
Input signal range
-1000 mV - 1000 mV
Measuring range span
Min. 50 K with thermocouple, 10% of the nominal span of the respective range with mV sources

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
12.5 mm
Height
112.5 mm
Depth
114.5 mm

Connection data

Connection method
Screw connection
Stripping length
7 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 14
Torque
0.5 Nm - 0.6 Nm

Output data

Signal output
Current output
Configurable/programmable
Yes
Current output signal
0 mA - 20 mA
Current output signal
4 mA - 20 mA (SIL)
Load/output load current output
≤ 600 Ω
Output ripple (current)
< 15 µAPP
Behavior in the event of a sensor error
As per NE 43 or can be freely defined

Ambient conditions

Ambient temperature (operation)
-40 °C - 70 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C - 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % - 95 % (non-condensing)
Degree of protection
IP20
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
1 %
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Conformance
CE-compliant, additionally EN 61326
ATEX
II 3 G Ex ec ic IIC T4 Gc
IECEx
Ex ec ic IIC T4 Gc
DNV GL-Temperature
B
DNV GL-Humidity
B
DNV GL-Vibration
A
DNV GL-EMC
B
DNV GL-Enclosure
Required protection according to the Rules shall be provided upon installation on board

Power supply

Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC - 30 V DC (24 V DC -20%...+25%)
Max. current consumption
< 40 mA (24 V DC)
Power dissipation
≤ 0.76 W
Power consumption
≤ 1 W