Temperature measuring transducer - MACX MCR-RTD-I-SP-C - 1052464
1052464
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Input data

Sensor types (RTD) that can be used
Pt, Ni, Cu sensors: 2, 3, 4-wire
Temperature measuring range
-200 °C - 850 °C (Range depending on the sensor type)
Input signal range
0 Ω - 50 kΩ
Potentiometer resistance range
0 Ω - 50 kΩ
Max. permissible overall conductor resistance
50 Ω (Per cable)
Sensor input current
10 µA - 210 µA (Up to 2x 210 µA with 3-conductor technology)
Measuring range span
≥ 50 K

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
12.5 mm
Height
116 mm
Depth
114.5 mm

Connection data

Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section solid
0.2 mm² - 1.5 mm²
Conductor cross section flexible
0.2 mm² - 1.5 mm²
Conductor cross section AWG
24 - 16

Output data

Signal output
Current output
Configurable/programmable
Yes
Current output signal
0 mA - 20 mA
Current output signal
4 mA - 20 mA (SIL)
Max. current output signal
≥ 21 mA
Load/output load current output
≤ 600 Ω
Output ripple (current)
< 15 µAPP
Behavior in the event of a sensor error
As per NE 43 or can be freely defined

Ambient conditions

Ambient temperature (operation)
-40 °C - 70 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C - 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % - 95 % (non-condensing)
Degree of protection
IP20
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
1 %
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Conformance
CE-compliant, additionally EN 61326
ATEX
II 3 G Ex ec ic IIC T4 Gc
IECEx
Ex ec ic IIC T4 Gc
DNV GL-Temperature
B
DNV GL-Humidity
B
DNV GL-Vibration
A
DNV GL-EMC
B
DNV GL-Enclosure
Required protection according to the Rules shall be provided upon installation on board

Power supply

Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC - 30 V DC (24 V DC -20%...+25%)
Power dissipation
≤ 0.76 W
Power consumption
≤ 1 W