Temperature measuring transducer - MACX MCR-EX-RTD-I-SP-C - 1052652
1052652
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Input data

Sensor types (RTD) that can be used
Sensors (2-, 3-, 4-wire)
Temperature measuring range
-200 °C - 850 °C (Range depending on the sensor type)
Input signal range
0 Ω - 50 kΩ
Potentiometer resistance range
0 Ω - 50 kΩ
Max. permissible overall conductor resistance
50 Ω (Per cable)
Sensor input current
10 µA - 210 µA (Up to 2x 210 µA with 3-conductor technology)
Measuring range span
≥ 50 K

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
12.5 mm
Height
116 mm
Depth
114.5 mm

Connection data

Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section solid
0.2 mm² - 1.5 mm²
Conductor cross section flexible
0.2 mm² - 1.5 mm²
Conductor cross section AWG
24 - 16

Output data

Signal output
Current output
Configurable/programmable
Yes
Current output signal
0 mA - 20 mA
Current output signal
4 mA - 20 mA (SIL)
Load/output load current output
≤ 600 Ω
Output ripple (current)
< 15 µAPP
Behavior in the event of a sensor error
As per NE 43 or can be freely defined

Ambient conditions

Ambient temperature (operation)
-40 °C - 70 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C - 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % - 95 % (non-condensing)
Degree of protection
IP20
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
1 %

Safety data

Max. internal capacitance Ci
44 nF
Max. output voltage Uo
6 V
Max. output current Io
16.6 mA (RTD in 4-wire technology)
Max. output power Po
25.2 mW (Linear)
Group
IIC/IIB/IIA
Max. external inductivity Lo
100 mH
Max. external capacitance Co
40 µF
Safety-related maximum voltage Um
253 V AC (125 V DC, Zone 2: 3.1, 3.2 = 30 V DC)
Input voltage Ui
7 V
Input current Ii
100 mA
Input power Pi
550 mW
Max. internal capacitance Ci
47 µF
Max. output voltage Uo
3.5 V
Max. output current Io
400 mA
Max. output power Po
350 mW
Group
IIC
Max. external inductivity Lo
20 µH
Max. external capacitance Co
2 µF

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Conformance
CE-compliant, additionally EN 61326
ATEX
I (M1) [Ex ia Ma] I
ATEX
II (1) G [Ex ia Ga] IIC
ATEX
II (1) D [Ex ia Da] IIIC
ATEX
II 3(1) G Ex ec ic [ia Ga] IIC T4 Gc
IECEx
[Ex ia Ma] I
IECEx
[Ex ia Ga] IIC
IECEx
[Ex ia Da] IIIC
IECEx
Ex ec ic [ia Ga] IIC T4 Gc
IECEx
Ex ec ic IIC T4 Gc
DNV GL-Temperature
B
DNV GL-Humidity
B
DNV GL-Vibration
A
DNV GL-EMC
B
DNV GL-Enclosure
Required protection according to the Rules shall be provided upon installation on board
Group
IIC/IIB/IIA
Group
IIC

Power supply

Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC - 30 V DC (24 V DC -20%...+25%)
Power dissipation
≤ 0.76 W
Power consumption
≤ 1 W