Type 2 surge protection base element - VAL-MS-T1/T2 3+1-BE/FM/10 - 1065864
1065864
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price

Additional Information

Part Number
1065864
UPC
4055626730165
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Basic element for surge protection device
Class Code : EC000472
Version : 7

Dimensions

Height
98.7 mm
Width
71 mm
Depth
51.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch
4 Div.

Connection data

Connection method
Screw connection
Screw thread
M5
Tightening torque
3 Nm (1.5 mm² - 16 mm²)
Tightening torque
4.5 Nm (25 mm² - 35 mm²)
Stripping length
16 mm
Conductor cross section flexible
1.5 mm² - 25 mm²
Conductor cross section solid
1.5 mm² - 35 mm²
Conductor cross section AWG
15 - 2
Connection method
Fork-type cable lug
Conductor cross section flexible
1.5 mm² - 16 mm²

Indicator/remote signaling

Switching function
PDT contact
Operating voltage
5 V AC - 250 V AC
Operating voltage
30 V DC
Operating current
5 mA AC - 750 mA AC
Operating current
1 A DC
Connection method
Plug-in/screw connection via COMBICON
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section flexible
0.14 mm² - 1.5 mm²
Conductor cross section solid
0.14 mm² - 1.5 mm²
Conductor cross section AWG
28 - 16

Ambient conditions

Degree of protection
IP20 (only when all terminal points are used)
Ambient temperature (operation)
-40 °C - 80 °C
Ambient temperature (storage/transport)
-40 °C - 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % - 95 %
Shock (operation)
30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
7.5g (10 - 500 Hz / 2.5 h / X, Y, Z)

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1

Protective circuit

Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
500 V AC
Rated load current IL
80 A
Short-circuit current rating ISCCR
25 kA
Max. backup fuse with V-type through wiring
80 A (gG)
Max. backup fuse with branch wiring
125 A (gG)

Standards and Regulations

Standards/regulations
IEC 61643-11 2011
Standards/regulations
EN 61643-11 2012