Front adapters - FLKM 14-PA-AB/1756/IN/EXTC - 2302874
2302874
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:

Additional Information

Part Number
2302874
UPC
4017918917531
Country of Origin
DE
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Accessories for controls
Class Code : EC002584
Version : 7

Supported controller

Controller
ALLEN-BRADLEY ControlLogix
Suitable I/O card
1756-IN16
Suitable I/O card
1756-IA16
Suitable I/O card
1756-IB16
Suitable I/O card
1756-IC16
Controller
HONEYWELL Experion PKS C200
Suitable I/O card
TC-IDA 161

Note

Type of note
Notes on operation
Note
Do not connect adjacent channels to SELV/ PELV and voltages dangerous to the touch.
Note
No additional touch protection is required when using a SELV/PELV voltage (≤ 25 V AC or 60 V DC).
Note
At least one functional insulation against adjacent modules is complied with (in the support rail direction). If the application has stricter requirements for the insulation (basic insulation or reinforced insulation), they must be realized by applying suitable measures (e. g. partition plates).

Connection data 2

Connection name
Supply
Connection method
Screw connection
Conductor cross section solid
0.14 mm² - 1.5 mm²
Conductor cross section flexible
0.14 mm² - 1.5 mm²
Conductor cross section AWG
28 - 16

Connection data

Connection name
Field level
Connection method
IDC/FLK pin strip
Number of connections
2
Number of positions
14
Pitch
2.54 mm

Ambient conditions

Ambient temperature (operation)
-20 °C - 50 °C
Ambient temperature (storage/transport)
-20 °C - 70 °C
Maximum altitude
≤ 2000 m
Degree of protection
IP00
Degree of protection
≥ IP54 (Installation location)

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Standards and Regulations

Connection in acc. with standard
CUL
Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Rated insulation voltage
63 V
Rated surge voltage
0.6 kV
Insulation
Functional insulation
Pollution degree
2
Overvoltage category
II

CAD Models