Phoenix Contact
2701159
Inline terminal 2701159
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price
Additional Information
- Part Number
- 2701159
- UPC
- 4046356713849
- Country of Origin
- DE
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 48.8 mm
- Height
- 136.8 mm
- Depth
- 71.5 mm
- Note on dimensions
- Housing dimensions
Ambient conditions
- Ambient temperature (operation)
- -25 °C - 55 °C (Standard)
- Ambient temperature (operation)
- -40 °C - 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
- Permissible humidity (operation)
- 10 % - 95 % (according to DIN EN 61131-2)
- Permissible humidity (storage/transport)
- 10 % - 95 % (according to DIN EN 61131-2)
- Air pressure (operation)
- 70 kPa - 106 kPa (up to 3000 m above sea level)
- Air pressure (storage/transport)
- 70 kPa - 106 kPa (up to 3000 m above sea level)
- Degree of protection
- IP20
Environmental Product Compliance
- China RoHS
- Environmentally friendly use period: unlimited = EFUP-e
- China RoHS
- No hazardous substances above threshold values
Analog inputs
- Description of the input
- Single-ended inputs, voltage or current
- Input name
- Analog inputs
- Number of inputs
- 8
- Connection method
- Inline shield connector
- Connection technology
- 2-wire
- Note regarding the connection technology
- shielded
- A/D conversion time
- approx. 10 µs
- Resolution A/D
- 16 bit
- Limit frequency (3 dB)
- 3.5 kHz
- Type of protection
- Surge protection, overcurrent protection
- Data formats
- IB IL, IB ST, IB RT, standardized representation, PIO format
- Measuring principle
- Successive approximation
- Measured value resolution
- 16 bits (15 bits + sign bit)
- Measured value representation
- 16 bit two's complement
- Current input signal
- 0 mA - 20 mA
- Current input signal
- 4 mA - 20 mA
- Current input signal
- -20 mA - 20 mA
- Current input signal
- 0 mA - 40 mA
- Current input signal
- -40 mA - 40 mA
- Input resistance current input
- 25 Ω (Shunt)
- Voltage input signal
- 0 V - 5 V
- Voltage input signal
- -5 V - 5 V
- Voltage input signal
- 0 V - 10 V
- Voltage input signal
- -10 V - 10 V
- Voltage input signal
- 0 V - 25 V
- Voltage input signal
- -25 V - 25 V
- Voltage input signal
- 0 V - 50 V
- Input resistance of voltage input
- > 240 kΩ
- Filtering
- 1st order low pass
Electrical isolation
- Test section
- 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min.
- Test section
- 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min.
- Test section
- 7.5 V supply (bus logic), 24 V supply UANA / I/O 500 V AC 50 Hz 1 min.
- Test section
- 7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V AC 50 Hz 1 min.
- Test section
- I/O / functional earth ground 500 V AC 50 Hz 1 min.
Interfaces
- Designation
- Inline local bus
- Connection method
- Inline data jumper
- Transmission speed
- 500 kbps
- Transmission physics
- Copper
Standards and Regulations
- Connection in acc. with standard
- CUL
- Protection class
- III, IEC 61140, EN 61140, VDE 0140-1
Inline potentials
- Designation
- Communications power (UL)
- Supply voltage
- 7.5 V DC (via voltage jumper)
- Current consumption
- typ. 48 A
- Current consumption
- max. 55 mA
- Designation
- Supply of analog modules (UANA)
- Supply voltage
- 24 V DC
- Supply voltage range
- 19.2 V DC - 30 V DC (including all tolerances, including ripple)
- Current consumption
- typ. 24 mA
- Current consumption
- max. 35 mA