Distributed I/O device - AXL E ETH DI8 DO8 M12 6M - 2701537
2701537
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
$1,113.73
1
Payment methods:
A total of 1 Part In-Stock from 7 Distributors

Additional Information

Part Number
2701537
UPC
4046356763851
Country of Origin
DE
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Fieldbus, decentr. periphery - digital I/O module
Class Code : EC001599
Version : 7

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
60 mm
Height
185 mm
Depth
38 mm
Note on dimensions
The height is 194.5 mm including the mounting plate. With fixing clips pulled out, the height is 212 mm. The depth is 38 mm including the mounting plate (30.5 mm without the mounting plate).
Drill hole spacing
198.5 mm

System limits of the bus coupler

Designation
Modbus/TCP
Equipment type
Modbus slave (server)
System-specific protocols
Modbus protocols Modbus/TCP
Protocols supported
SNMP v1
Protocols supported
HTTP
Protocols supported
TFTP
Protocols supported
FTP
Protocols supported
BootP
Protocols supported
DHCP
Specification
Modbus application protocol V1.1b

Supply

Designation
Module electronics and sensors (US)
Connection method
M12 connector (T-coded)
Number of positions
4
Supply voltage
24 V DC
Current consumption
typ. 190 mA ±15 % (at 24 V DC)
Designation
Actuators (UA)
Supply voltage range
18 V DC - 31.2 V DC (including all tolerances, including ripple)
Current consumption
typ. 30 mA ±15 % (at 24 V DC)

Digital inputs

Input name
Digital inputs
Description of the input
EN 61131-2 types 1 and 3
Connection method
M12 connector, double occupancy
Connection technology
4-wire
Number of inputs
8
Protective circuit
Overload protection, short-circuit protection of sensor supply
Nominal input voltage UIN
24 V DC
Nominal input current at UIN
typ. 3 mA
Input filter time
< 1000 µs
Cable length
max. 30 m (To the sensor)
Input voltage range "0" signal
0 V - 5 V DC
Input voltage range "1" signal
11 V DC - 30 V DC

Ambient conditions

Ambient temperature (operation)
-25 °C - 60 °C
Ambient temperature (storage/transport)
-25 °C - 85 °C
Permissible humidity (operation)
5 % - 95 %
Permissible humidity (storage/transport)
5 % - 95 %
Air pressure (operation)
70 kPa - 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa - 106 kPa (up to 3000 m above sea level)
Degree of protection
IP65/IP67

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Electrical isolation

Test section
24 V supply (communications power and sensor supply, digital inputs)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min.
Test section
24 V supply (communications power and sensor supply, digital inputs)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
Test section
24 V supply (communications power and sensor supply, digital inputs)/FE 500 V AC 50 Hz 1 min.
Test section
Bus connection (Ethernet 1)/FE 500 V AC 50 Hz 1 min.
Test section
Bus connection (Ethernet 2)/FE 500 V AC 50 Hz 1 min.
Test section
Bus connection (Ethernet 1)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
Test section
24 V supply (actuator supply, digital outputs)/24 V supply (communications power and sensor supply, digital inputs) 500 V AC 50 Hz 1 min.
Test section
24 V supply (actuator supply, digital outputs)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min.
Test section
24 V supply (actuator supply, digital outputs)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
Test section
24 V supply (actuator supply, digital outputs)/FE 500 V AC 50 Hz 1 min.

Digital outputs

Output name
Digital outputs
Connection method
M12 connector, double occupancy
Connection technology
3-wire
Number of outputs
8
Protective circuit
Overload protection, short-circuit protection of outputs yes
Output voltage
24 V DC
Nominal output voltage
24 V DC (from voltage UA)
Maximum output current per channel
500 mA
Nominal load, inductive
12 VA (1.2 H, 48 Ω, with nominal voltage)
Nominal load, ohmic
12 W (48 Ω, with nominal voltage)
Switching frequency
max. 5500 per second (with at least 50 mA load current)
Output voltage when switched off
max. 1 V
Output current when switched off
max. 20 µA
Behavior with overload
Auto restart
Reverse voltage resistance to short pulses
Reverse voltage proof

Interfaces

Designation
Ethernet
No. of channels
2
Connection method
M12 fast connection technology
Note on the connection method
D-coded
Designation connection point
Copper cable
Transmission speed
10/100 Mbps (with auto negotiation)
Number of positions
4

Standards and Regulations

Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Mechanical tests
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse
Mechanical tests
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)

CAD Models

Trace parts
Trace parts
Download