Phoenix Contact
2736699
Power supply unit - ASI QUINT 100-240/4.8 EFD - 2736699
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
$579.15
1
Payment methods:
A total of 17 Parts In-Stock from 9 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price
Additional Information
- Part Number
- 2736699
- UPC
- 4017918959685
- Country of Origin
- TH
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : DC-power supply
- Class Code : EC002540
- Version : 7
Input data
- Nominal input voltage range
- 100 V AC - 240 V AC
- AC frequency range
- 45 Hz - 65 Hz
- Frequency range DC
- 0 Hz
- Current consumption
- approx. 1.8 A (120 V AC)
- Current consumption
- 1 A (230 V AC)
- Nominal power consumption
- 144 W
- Inrush current
- < 15 A (typical)
- Mains buffering time
- > 60 ms (120 V AC)
- Mains buffering time
- > 100 ms (230 V AC)
- Input fuse
- 5 A (slow-blow, internal)
- Recommended breaker for input protection
- 6 A - 16 A (Characteristics B, C, D, K)
Dimensions
- Width
- 70 mm
- Height
- 145 mm
- Depth
- 125 mm
- Width with alternative assembly
- 122 mm
- Height with alternative assembly
- 145 mm
- Depth with alternative assembly
- 73 mm
Output data
- Nominal output voltage
- 30.1 V DC ±1.5 %
- Nominal output current (IN)
- 4.8 A
- Connection in parallel
- No
- Connection in series
- yes
- Residual ripple
- < 30 mVPP
- Output power
- 144 W
- Typical response time
- < 0.5 s
- Peak switching voltages nominal load
- < 50 mVPP
- Maximum power dissipation in no-load condition
- 4 W
- Power loss nominal load max.
- 16 W
Connection data, input
- Connection method
- Pluggable spring-cage connection
- Conductor cross section solid min.
- 0.2 mm²
- Conductor cross section solid max.
- 2.5 mm²
- Conductor cross section flexible min.
- 0.2 mm²
- Conductor cross section flexible max.
- 2.5 mm²
- Conductor cross section AWG min.
- 24
- Conductor cross section AWG max.
- 12
- Stripping length
- 10 mm
- Screw thread
- M3
Connection data, output
- Connection method
- Spring-cage connection
- Conductor cross section solid min.
- 0.2 mm²
- Conductor cross section solid max.
- 2.5 mm²
- Conductor cross section flexible min.
- 0.2 mm²
- Conductor cross section flexible max.
- 2.5 mm²
- Conductor cross section AWG min.
- 24
- Conductor cross section AWG max.
- 12
- Screw thread
- M3
Ambient conditions
- Degree of protection
- IP20
- Ambient temperature (operation)
- -25 °C - 70 °C (> 60 °C Derating: 2.5 %/K)
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
- Max. permissible relative humidity (operation)
- 95 % (at 25 °C, non-condensing)
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Standards and Regulations
- Electromagnetic compatibility
- Conformance with EMC Directive 2014/30/EU
- Noise immunity
- EN 61000-6-2
- Connection in acc. with standard
- CUL
- Contact discharge
- 4 kV (Test Level 2)
- Standards/regulations
- EN 61000-4-3
- Frequency range
- 80 MHz - 1 GHz
- Test field strength
- 10 V/m
- Frequency range
- 1.4 GHz - 2 GHz
- Test field strength
- 3 V/m
- Standards/regulations
- EN 61000-4-4
- Comments
- Criterion B
- Signal
- 1 kV (Test Level 2 - asymmetrical)
- Standards/regulations
- EN 61000-4-6
- Frequency range
- 0.15 MHz - 80 MHz
- Voltage
- 10 V (Test Level 3)
- Low Voltage Directive
- Conformance with Low Voltage Directive 2014/35/EC
- Standard - Safety of transformers
- EN 61558-2-17
- Standard - Electrical safety
- EN 60950-1/VDE 0805 (SELV)
- Standard - Electrical safety
- DIN VDE 0100-410
- Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
- EN 50178/VDE 0160 (PELV)
- Standard - Safe isolation
- DIN VDE 0100-410
- Standard - Safe isolation
- DIN VDE 0106-1010
- Standard – Limitation of mains harmonic currents
- EN 61000-3-2
- UL approvals
- UL/C-UL listed UL 508
- UL approvals
- UL/C-UL Recognized UL 60950-1