Resistance/potiposition transducer - MINI MCR-SL-R-UI-SP - 2810256
2810256
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:On Request
Best price:
793,80 zł

Additional Information

Part Number
2810256
UPC
4017918996079
Country of Origin
DE
ETIM
Group Code : EG000026
Group Description : Sensors
Class Description : Isolation amplifier
Class Code : EC002653
Version : 7

Input data

Potentiometer
100 Ω - 100 kΩ
Reference voltage source
< 3.6 V

Dimensions

Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm

Connection data

Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 12

Output data

Voltage output signal
0 V - 5 V
Voltage output signal
1 V - 5 V
Voltage output signal
0 V - 10 V
Voltage output signal
10 V - 0 V
Current output signal
0 mA - 20 mA
Current output signal
4 mA - 20 mA
Current output signal
20 mA - 0 mA
Current output signal
20 mA - 4 mA
Max. voltage output signal
12.5 V
Max. current output signal
23 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω (20 mA)

Ambient conditions

Ambient temperature (operation)
-20 °C - 65 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % - 95 % (non-condensing)
Degree of protection
IP20
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Environmental Product Compliance

China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
5 %
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Connection in acc. with standard
CUL
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
Basic insulation according to EN 61010
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Recognized
UL, USA/Canada
Class I, Div. 2, Groups A, B, C, D T4

Power supply

Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption
< 25 mA (at 24 V DC)
Power consumption
< 500 mW