Temperature measuring transducer 2810298
2810298
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Input data

Number of inputs
1
Configurable/programmable
Yes, preconfigured
Sensor types (RTD) that can be used
Pt 100 (IEC 60751/EN 60751)
Sensor input current
1 mA (constant)
Connection technology
2, 3, 4-wire

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm

Connection data

Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
26
Conductor cross section AWG max.
12
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Stripping length
12 mm
Screw thread
M3

Output data

Number of outputs
1
Configurable/programmable
Yes, preconfigured
Current output signal
4 mA - 20 mA
Current output signal
20 mA - 4 mA
Max. output current
23 mA (output limit)
Load/output load current output
(Usupply - 12 V) / 22 mA
Ripple
< 20 mVPP (at 500 Ω)

Ambient conditions

Ambient temperature (operation)
-20 °C - 65 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Maximum altitude
≤ 2000 m

Environmental Product Compliance

China RoHS
Environmentally Friendly Use Period = 50
China RoHS
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
5 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
5 %
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
5 %

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Standards/regulations
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
Basic insulation according to EN 61010
Conformance
CE-compliant
ATEX
 II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Recognized
UL, USA/Canada
Class I, Div. 2, Groups A, B, C, D T4
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2

Power supply

Designation
Loop-powered
Supply voltage range
12 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption
< 4.5 mA (without signal current)
Power consumption
< 150 mW (without signal current)