Temperature measuring transducer - MACX MCR-EX-T-UI-UP-C - 2811763
2811763
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Input data

Sensor types (RTD) that can be used
Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC)
B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range
-250 °C - 2500 °C (Range depending on the sensor type)
Input signal range
0 Ω - 50 kΩ
Potentiometer resistance range
0 Ω - 50 kΩ
Input signal range
-1000 mV - 1000 mV

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
17.5 mm
Height
112.8 mm
Depth
113.7 mm

Connection data

Connection method
Screw connection
Stripping length
7 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 14
Torque
0.5 Nm - 0.6 Nm

Output data

Max. voltage output signal
± 11 V
Current output signal
4 mA - 20 mA (in the case of SIL; further free configuration without SIL)
Max. current output signal
22 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 600 Ω (at 20 mA)
Behavior in the event of a sensor error
according to NE 43 or freely configurable
Output name
Switching output
Contact type
1 PDT
Contact material
AgSnO₂, hard gold-plated
Maximum switching voltage
30 V AC (30 V DC)
Maximum inrush current
0.5 A (30 V AC)
Maximum inrush current
1 A (30 V DC)
Mechanical service life
1x 10⁵ cycles

Ambient conditions

Ambient temperature (operation)
-20 °C - 65 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
typ. 5 % - 95 % (non-condensing)
Degree of protection
IP20 (not assessed by UL)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Shock
15g, according to IEC 60068-2-27
Vibration (operation)
5g, accordance to IEC 60068-2-6

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
2 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6

Safety data

Max. internal inductance Li
negligible
Max. internal capacitance Ci
44 nF
Max. output voltage Uo
6 V
Max. output current Io
7.4 mA
Max. output power Po
11 mW
Group
IIC
Max. external inductivity Lo
100 mH
Max. external capacitance Co
1.3 µF
Max. external inductivity Lo
10 mH
Max. external capacitance Co
1.7 µF
Max. external inductivity Lo
1 mH
Max. external capacitance Co
2.6 µF
Group
IIB
Max. external capacitance Co
6.8 µF
Max. external capacitance Co
9.2 µF
Max. external capacitance Co
15 µF
Safety-related maximum voltage Um
253 V AC/DC

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
4-way, between input/output/power supply/switching output
Shock
15g, according to IEC 60068-2-27
Vibration (operation)
5g, accordance to IEC 60068-2-6
Conformance
CE-compliant
ATEX
II (1) G [Ex ia Ga] IIC
ATEX
II (1) D [Ex ia Da] IIIC
ATEX
II 3 G Ex nA nC ic IIC T4 Gc X
IECEx
[Ex ia Ga] IIC
IECEx
[Ex ia Da] IIIC
IECEx
Ex nA nC ic IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
DNV GL-Temperature
B
DNV GL-Humidity
B
DNV GL-Vibration
A
DNV GL-EMC
A
DNV GL-Enclosure
Required protection according to the Rules shall be provided upon installation on board
Group
IIC
Group
IIB

Power supply

Supply voltage range
24 V - 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Typical current consumption
< 50 mA (24 V DC)
Power consumption
< 1.5 W