Current transducers - MCR-S-10/50-UI-SW-DCI - 2814663
2814663
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€51.07
1
Payment methods:
A total of 4 Parts In-Stock from 2 Distributors

Additional Information

Part Number
2814663
Country of Origin
DE
ETIM
Group Code : EG000026
Group Description : Sensors
Class Description : Current value transformer
Class Code : EC002475
Version : 7

Input data

Input
Current measuring input
Configurable/programmable
Yes, preconfigured
Operate threshold
0.8 % (of measuring range nominal value 50 A)
Setting range for min. input current
0 A - 9.5 A
Setting range for max. input current
0 A - 55 A
Impulse form
AC, DC or distorted currents
Overload capacity
Depending on through connected conductor
Surge strength
Depending on through connected conductor
Frequency measuring range
15 Hz - 400 Hz
Connection method
Through connection, diameter 10.5 mm

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
22.5 mm
Height
99 mm
Depth
114.5 mm

Connection data

Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 14

Output data

Output name
Voltage output / current output
Configurable/programmable
Yes, preconfigured
Voltage output signal
0 V - 10 V
Voltage output signal
2 V - 10 V
Voltage output signal
-10 V - 10 V
Voltage output signal
0 V - 5 V
Voltage output signal
1 V - 5 V
Voltage output signal
-5 V - 5 V
Voltage output signal
10 V - 0 V
Voltage output signal
10 V - 2 V
Voltage output signal
10 V - -10 V
Voltage output signal
5 V - 0 V
Voltage output signal
5 V - 1 V
Voltage output signal
5 V - -5 V
Current output signal
0 mA - 20 mA
Current output signal
4 mA - 20 mA
Current output signal
20 mA - 0 mA
Current output signal
20 mA - 4 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω

Ambient conditions

Ambient temperature (operation)
-20 °C - 60 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Maximum altitude
< 2000 m
Degree of protection
IP20
Noise immunity
EN 61000-6-2

Conformance/approvals

Designation
CE
Identification
CE-compliant
Designation
UL, USA/Canada
Identification
Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
Identification
Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Switching output

Output name
Relay output
Contact type
1 PDT
Contact material
AgSnO, hard gold-plated
Maximum switching voltage
30 V AC
Maximum switching voltage
36 V DC
Maximum switching voltage
250 V AC
Limiting continuous current
50 mA (for gold layer, 30 V AC/ 36 V DC)
Limiting continuous current
2 A (in case of a destroyed gold layer, 250 V AC)
Output name
Transistor output, pnp
Output voltage range
19 V - 29 V (supply voltage - 1 V)
Continuous load current
80 mA (Not short-circuit proof)
Setting range of the threshold value
1 % - 110 %
Setting range of the response delay
0.1 s - 20 s
Status display
Yellow LED

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2
Connection in acc. with standard
CUL
Low Voltage Directive
Conformance with Low Voltage Directive
Conformance
CE-compliant
UL, USA/Canada
Class I, Zone 2, AEx nA nC IIC T4, Ex nA nC IIC T4 Gc X
UL, USA/Canada
Class I, Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only

Power supply

Supply voltage range
20 V DC - 30 V DC
Max. current consumption
< 50 mA (without load)