Surge protection device - TT-2-PE-110AC - 2858483
2858483
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.
Offer with manufacturer lead time
Ships in:On Request
Best price:
249,07 zł

Additional Information

Part Number
2858483
UPC
4017918893156
Country of Origin
DE
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Surge protection device for data networks/MCR-technology
Class Code : EC000943
Version : 7

Dimensions

Height
79.6 mm
Width
6.2 mm
Depth
54.6 mm

Connection data

Connection method
Screw connection
Connection method IN
Screw terminal blocks
Connection method OUT
Screw terminal blocks
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8 mm
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section solid
0.2 mm² - 4 mm²
Conductor cross section AWG
24 - 14

Ambient conditions

Ambient temperature (operation)
-40 °C - 85 °C
Altitude
≤ 2000 m
Degree of protection
IP20

Environmental Product Compliance

China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Protective circuit

IEC test classification
C1
IEC test classification
C2
IEC test classification
C3
IEC test classification
D1
Nominal voltage UN
110 V AC
Maximum continuous voltage UC
120 V AC
Rated current
300 mA (30 °C)
Operating effective current IC at UC
≤ 5 µA
Residual current IPE
≤ 10 µA
Nominal discharge current In (8/20) µs (line-line)
5 kA
Nominal discharge current In (8/20) µs (line-earth)
5 kA
Pulse discharge current Iimp (10/350) µs
500 A
Total discharge current Itotal (8/20) µs
10 kA
Max. discharge current Imax (8/20) µs maximum (line-line)
5 kA
Max. discharge current Imax (8/20) µs maximum (line-earth)
5 kA
Nominal pulse current Ian (10/1000) µs (line-earth)
100 A
Output voltage limitation at 1 kV/µs (line-line) spike
≤ 250 V
Output voltage limitation at 1 kV/µs (line-earth) spike
≤ 650 V
Voltage protection level Up (line-line)
≤ 300 V (C2 - 10 kV / 5 kA)
Voltage protection level Up (line-line)
≤ 250 V (C1 - 1 kV/500 A)
Voltage protection level Up (line-earth)
≤ 900 V (C2 - 10 kV / 5 kA)
Voltage protection level Up (line-earth)
≤ 650 V (C1 - 1 kV/500 A)
Voltage protection level Up (line-earth)
≤ 850 V (C3 - 10 A)
Voltage protection level Up (line-earth)
≤ 900 V (C3 - 100 A)
Voltage protection level Up (line-earth)
≤ 800 V (D1 - 500 A)
Response time tA (line-line)
≤ 1 ns
Response time tA (line-earth)
≤ 100 ns
Input attenuation aE, sym.
typ. 1.5 dB (≤ 2 MHz)
Input attenuation aE, sym.
typ. 0.6 dB (≤ 500 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system
typ. 15 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
typ. 8 MHz
Capacity (line-line)
typ. 600 pF
Capacity (line-earth)
≤ 2 pF
Resistance per path
9.4 Ω 10 %
Surge protection fault message
none
Max. required back-up fuse
315 mA (T/IEC 60127-2/3)
Impulse durability (line-line)
C1 - 1 kV / 500 A
Impulse durability (line-line)
C2 - 10 kV / 5 kA
Impulse durability (line-earth)
C1 - 1 kV / 500 A
Impulse durability (line-earth)
C2 - 10 kV / 5 kA
Impulse durability (line-earth)
C3 - 100 A
Impulse durability (line-earth)
D1 - 500 A
Alternating current carrying capacity (line-line)
0.1 A - 1 s
Alternating current carrying capacity (line-earth)
1 A - 1 s

Standards and Regulations

Standards/regulations
IEC 61643-21
Standards/regulations
EN 61643-21
Standards/specifications
IEC 61643-21/A1 2008
Standards/specifications
EN 61643-21/A1 2009