Phoenix Contact
2864561
Temperature measuring transducer - MCR-FL-T-LP-I - 2864561
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
1007,98 zł
Additional Information
- Part Number
- 2864561
- UPC
- 4017918899820
- Country of Origin
- DE
- ETIM
- Group Code : EG000026
- Group Description : Sensors
- Class Description : Temperature transmitter
- Class Code : EC002919
- Version : 7
Input data
- Configurable/programmable
- Yes, programmable
- Sensor types (RTD) that can be used
- Pt, Ni (100, 500, 1000); minimum measurement range 10 K
- Sensor types that can be used (TC)
- B, C, D, E, J, K, L, N, R, S, T, U; minimum measurement range 50 K/500 K
- Linear resistance measuring range
- Resistance-type sensor from 10 Ω to 400 Ω and from 10 Ω to 2000 Ω; minimum measurement range 10 Ω/100 Ω
- Connection technology
- 2, 3, 4-wire
Dimensions
- Width
- 12.5 mm
- Height
- 99 mm
- Depth
- 114.5 mm
Connection data
- Connection method
- Screw connection
- Stripping length
- 8 mm
- Screw thread
- M3
- Conductor cross section solid
- 0.2 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 14
Output data
- Output name
- Current output
- Number of outputs
- 1
- Configurable/programmable
- Yes
- Current output signal
- 4 mA - 20 mA
- Current output signal
- 20 mA - 4 mA
- Output current with wire break
- ≤ 3.6 mA or ≥ 21 mA (adjustable)
- Output current with short-circuit
- ≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples)
- Output current range with overrange/underrange
- ≤ 20.5 mA / ≥ 3.8 mA (linear increase/decrease)
- Load/output load current output
- max (Vsupply -12 V) / 0.023 A (current output)
Ambient conditions
- Ambient temperature (operation)
- -40 °C - 85 °C
- Degree of protection
- IP20
- Noise immunity
- EN 61326-1 (IEC 61326) and NAMUR NE 21
Environmental Product Compliance
- China RoHS
- Environmentally friendly use period: unlimited = EFUP-e
- China RoHS
- No hazardous substances above threshold values
Standards and Regulations
- Noise emission
- EN 61326-1 (IEC 61326) and NAMUR NE 21
- Noise immunity
- EN 61326-1 (IEC 61326) and NAMUR NE 21
- Connection in acc. with standard
- CUL
- Conformance
- CE-compliant
- UL, USA/Canada
- Class I, Div. 2, Groups A, B, C, D
Power supply
- Designation
- Loop-powered
- Supply voltage range
- 12 V DC - 35 V DC
- Max. current consumption
- < 3.5 mA
Other Categories
NanometersManometersFlowmetersSensorsAcceleration SensorsFiber Optic SensorsDetectorsUltrasonic SensorsTemperature & Humidity SensorsVibration SensorsLevel SensorsPressure SensorsProximity SensorsInductive SensorsMotion SensorsMagnetic Sensors GroupOptical SensorsCapacitive SensorsPhotoelectric SensorsPosition SensorsEncodersOther sensors and Accessories