Phoenix Contact
2864781
1 / 1
Description
MCR passive isolator, 2-channel, for the electrical isolation of current signals without auxiliary power, with spring-cage connection- Country of Origin
- DE
- Part Number
- 2864781
- Tariff Code
- 85437090
- EAN
- 4017918974961
- UPC
- 4017918974961
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 7 pcs.In-StockUpdated at: 28-10-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- Used
Used - A previously used item with possible signs of cosmetic wear. It is fully operational and functions as intended, though the original packaging may be missing.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Input data
- Description of the input
- Current input
- Number of inputs
- 2
- Configurable/programmable
- no
- Current input signal
- 0 mA - 20 mA
- Current input signal
- 4 mA - 20 mA
- Max. input voltage
- 18 V
- Max. input current
- 40 mA
- Response current
- approx. 190 µA
- Input voltage limitation
- < 2 V (20 mA)
- Voltage dissipation
- 1.9 V (I = 20 mA)
Dimensions
- Width
- 6.2 mm
- Height
- 93.1 mm
- Depth
- 102.5 mm
Connection data
- Connection method
- Spring-cage connection
- Conductor cross section solid min.
- 0.2 mm²
- Conductor cross section solid max.
- 2.5 mm²
- Conductor cross section AWG min.
- 24
- Conductor cross section AWG max.
- 12
- Conductor cross section flexible min.
- 0.2 mm²
- Conductor cross section flexible max.
- 2.5 mm²
- Stripping length
- 8 mm
Output data
- Output name
- Current output
- Number of outputs
- 2
- Configurable/programmable
- no
- Current output signal
- 0 mA - 20 mA
- Current output signal
- 4 mA - 20 mA
- Load/output load current output
- < 600 Ω (at I = 20 mA output signal)
- Ripple
- < 10 mVrms (at 600 Ω)
- Transmission Behavior
- 1:1 to input signal
Ambient conditions
- Ambient temperature (operation)
- -20 °C - 65 °C
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
Environmental Product Compliance
- China RoHS
- Environmentally Friendly Use Period = 50
- China RoHS
- For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
EMC data
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Evaluation criterion
- A
- Designation
- Fast transients (burst)
- Standards/regulations
- EN 61000-4-4
- Evaluation criterion
- B
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Evaluation criterion
- A
Standards and Regulations
- Electromagnetic compatibility
- Conformance with EMC directive
- Noise emission
- EN 61000-6-4
- Connection in acc. with standard
- CUL
- Standards/regulations
- EN 61000-4-2
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Evaluation criterion
- A
- Standards/regulations
- EN 61000-4-4
- Standards/regulations
- EN 61000-4-5
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Evaluation criterion
- A
- Electrical isolation
- Basic insulation according to EN 61010
- Conformance
- CE-compliant
- ATEX
- II 3 G Ex nA II T6 X
- UL, USA/Canada
- UL 508 Recognized
- UL, USA/Canada
- Class I, Div. 2, Groups A, B, C, D
- GL
- GL EMC 2 D
- Fire protection for rail vehicles (DIN EN 45545-2) R22
- HL 1 - HL 2
- Fire protection for rail vehicles (DIN EN 45545-2) R23
- HL 1 - HL 2
- Fire protection for rail vehicles (DIN EN 45545-2) R24
- HL 1 - HL 2
Power supply
- Supply voltage range
- no separate supply voltage necessary
- Power consumption
- 34 mW (per channel)