Temperature measuring transducer - MACX MCR-SL-RTD-I - 2865065
2865065
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Input data

Sensor types (RTD) that can be used
Pt, Ni, Cu sensors: 2, 3, 4-wire
Temperature measuring range
-200 °C - 850 °C (Range depending on the sensor type)
Input signal range
0 Ω - 2000 Ω
Max. permissible overall conductor resistance
50 Ω (Per cable)
Sensor input current
200 µA - 1 mA
Measuring range span
> 50 K

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
12.5 mm
Height
112.5 mm
Depth
113.7 mm

Connection data

Connection method
Screw connection
Stripping length
7 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 14
Torque
0.5 Nm - 0.6 Nm

Output data

Signal output
Current output
Configurable/programmable
Yes
Current output signal
0 mA - 20 mA
Current output signal
4 mA - 20 mA
Load/output load current output
≤ 500 Ω
Output ripple (current)
< 50 µAPP
Behavior in the event of a sensor error
As per NE 43 or can be freely defined
Configurable/programmable
no

Ambient conditions

Ambient temperature (operation)
-20 °C - 60 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C - 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % - 95 % (non-condensing)
Degree of protection
IP20 (not assessed by UL)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6

Standards and Regulations

Noise emission
EN 61000-6-4
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Conformance
CE-compliant, additionally EN 61326-1
ATEX
II 3G Ex nA ic IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
UL, USA/Canada
UL 61010 Listed
UL, USA/Canada
Class I, Div. 2, Groups A, B, C, D T4
UL, USA/Canada
Class I, Zone 2, Group IIC T4
GL
C, EMC1

Power supply

Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC - 30 V DC (24 V DC -20%...+25%)
Max. current consumption
< 40 mA (24 V DC)
Power dissipation
< 1 W