Temperature measuring transducer - MACX MCR-EX-SL-TC-I - 2865942
2865942
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Input data

Input
Intrinsically safe
Sensor types that can be used (TC)
E, J, K, N as per IEC / EN 60584, L as per DIN 43760
Temperature measuring range
-250 °C - 1372 °C (Range depending on the sensor type)
Input signal range
-20 mV - 70 mV
Measuring range span
Min. 50 K for thermocouples, 3 mV for mV sources
Voltage input signal
-20 mV - 70 mV

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
12.5 mm
Height
106.4 mm
Depth
113.7 mm

Connection data

Connection method
Screw connection
Stripping length
7 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 14
Torque
0.5 Nm - 0.6 Nm

Output data

Signal output
Current output
Configurable/programmable
Yes
Current output signal
0 mA - 20 mA
Current output signal
4 mA - 20 mA
Load/output load current output
≤ 500 Ω
Output ripple (current)
< 50 µAPP
Behavior in the event of a sensor error
As per NE 43 or can be freely defined
Configurable/programmable
no

Ambient conditions

Ambient temperature (operation)
-20 °C - 60 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C - 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % - 95 % (non-condensing)
Degree of protection
IP20 (not assessed by UL)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6

Safety data

Max. output voltage Uo
6 V
Max. output current Io
4.7 mA
Max. output power Po
7 mW
Max. external capacitance Co
1.5 µF
Group
IIC
Max. external inductivity Lo
10 mH
Max. external capacitance Co
1.9 µF
Max. external inductivity Lo
1 mH
Max. external capacitance Co
2.7 µF
Group
IIB
Max. external inductivity Lo
100 mH
Max. external capacitance Co
7 µF
Max. external capacitance Co
9.4 µF
Max. external capacitance Co
15 µF
Safety-related maximum voltage Um
253 V AC (125 V DC)

Safety characteristic data

Safety Integrity Level (SIL)
2

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Conformance
CE-compliant, additionally EN 61326
ATEX
II (1) G [Ex ia Ga] IIC/IIB
ATEX
II (1) D [Ex ia Da] IIIC
ATEX
II 3(1) G Ex nA ic [ia Ga] IIC T4 Gc X
IECEx
[Ex ia Ga] IIC/IIB
IECEx
[Ex ia Da] IIIC
IECEx
Ex nA ic [ia Ga] IIC T4 Gc
UL, USA/Canada
Class I Div 2; IS for Class I, II, III Div 1
Group
IIC
Group
IIB

Power supply

Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC - 30 V DC (24 V DC -20%...+25%)
Max. current consumption
< 40 mA (24 V DC)
Power dissipation
< 1 W