Output signal conditioner - MACX MCR-SL-IDSI-I - 2865971
2865971
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
Send request for price

Additional Information

Part Number
2865971
UPC
4046356449540
Country of Origin
DE
ETIM
Group Code : EG000026
Group Description : Sensors
Class Description : Isolation amplifier
Class Code : EC002653
Version : 7

Input data

Current input signal
0 mA - 20 mA
Current input signal
4 mA - 20 mA
Input impedance
> 100 kΩ (If there is a line fault)
Voltage drop
5.4 V (20 mA)

Dimensions

Width
12.5 mm
Height
112.5 mm
Depth
113.7 mm

Connection data

Connection method
Screw connection
Stripping length
7 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 14
Torque
0.5 Nm - 0.6 Nm

Output data

Signal output
Current output
Current output signal
0 mA - 20 mA
Current output signal
4 mA - 20 mA
Transmission Behavior
1:1 to input signal
Load/output load current output
< 800 Ω (20 mA)
Load/output load current output
< 730 Ω (22.5 mA)
Output ripple
< 20 mVrms

Data communication (bypass)

HART function
Yes
Protocols supported
HART

Ambient conditions

Ambient temperature (operation)
-20 °C - 60 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C - 85 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
10 % - 95 % (non-condensing)
Degree of protection
IP20 (not assessed by UL)
Noise immunity
EN 61000-6-2

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3

Safety characteristic data

Integrity requirement
IEC 61508 - Low demand
Equipment type
Type A
Safety Integrity Level (SIL)
2
Safe Failure Fraction (SFF)
94.68 %
ΛSU
4.965 x 10-⁷ (496.5 FIT)
ΛSD
0
ΛDU
2.79 x 10-⁸ (27.9 FIT)
Probability of a hazardous failure on demand (PFDAVG)
1.22 x 10-⁴ (1 year)
Probability of a hazardous failure on demand (PFDAVG)
6.1 x 10-⁴ (5 years)
Probability of a hazardous failure on demand (PFDAVG)
12.2 x 10-⁴ (10 years)
Diagnostic coverage (DC)
DCS=0 %, DCD=0 %
Integrity requirement
IEC 61508 - High demand
ΛDD
0
Probability of a hazardous failure per hour (PFHD)
2,79 x 10-⁸

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Conformance
CE-compliant, additionally EN 61326-1
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
UL, USA/Canada
UL 61010 Listed
UL, USA/Canada
Class I, Div. 2, Groups A, B, C, D T4
UL, USA/Canada
Class I, Zone 2, Group IIC T4
DNV GL-Temperature
B
DNV GL-Humidity
B
DNV GL-Vibration
A
DNV GL-EMC
B
DNV GL-Enclosure
Required protection according to the Rules shall be provided upon installation on board

Power supply

Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC - 30 V DC (24 V DC -20%...+25%)
Max. current consumption
< 46 mA (24 V DC / 20 mA)
Power dissipation
< 1.1 W (24 V DC / 20 mA)