Phoenix Contact
2865971
Output signal conditioner - MACX MCR-SL-IDSI-I - 2865971
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Product Conditions:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
Send request for price
Additional Information
- Part Number
- 2865971
- UPC
- 4046356449540
- Country of Origin
- DE
- ETIM
- Group Code : EG000026
- Group Description : Sensors
- Class Description : Isolation amplifier
- Class Code : EC002653
- Version : 7
Input data
- Current input signal
- 0 mA - 20 mA
- Current input signal
- 4 mA - 20 mA
- Input impedance
- > 100 kΩ (If there is a line fault)
- Voltage drop
- 5.4 V (20 mA)
Dimensions
- Width
- 12.5 mm
- Height
- 112.5 mm
- Depth
- 113.7 mm
Connection data
- Connection method
- Screw connection
- Stripping length
- 7 mm
- Screw thread
- M3
- Conductor cross section solid
- 0.2 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 14
- Torque
- 0.5 Nm - 0.6 Nm
Output data
- Signal output
- Current output
- Current output signal
- 0 mA - 20 mA
- Current output signal
- 4 mA - 20 mA
- Transmission Behavior
- 1:1 to input signal
- Load/output load current output
- < 800 Ω (20 mA)
- Load/output load current output
- < 730 Ω (22.5 mA)
- Output ripple
- < 20 mVrms
Data communication (bypass)
- HART function
- Yes
- Protocols supported
- HART
Ambient conditions
- Ambient temperature (operation)
- -20 °C - 60 °C (Any mounting position)
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
- Maximum altitude
- ≤ 2000 m
- Permissible humidity (operation)
- 10 % - 95 % (non-condensing)
- Degree of protection
- IP20 (not assessed by UL)
- Noise immunity
- EN 61000-6-2
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
EMC data
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
Safety characteristic data
- Integrity requirement
- IEC 61508 - Low demand
- Equipment type
- Type A
- Safety Integrity Level (SIL)
- 2
- Safe Failure Fraction (SFF)
- 94.68 %
- ΛSU
- 4.965 x 10-⁷ (496.5 FIT)
- ΛSD
- 0
- ΛDU
- 2.79 x 10-⁸ (27.9 FIT)
- Probability of a hazardous failure on demand (PFDAVG)
- 1.22 x 10-⁴ (1 year)
- Probability of a hazardous failure on demand (PFDAVG)
- 6.1 x 10-⁴ (5 years)
- Probability of a hazardous failure on demand (PFDAVG)
- 12.2 x 10-⁴ (10 years)
- Diagnostic coverage (DC)
- DCS=0 %, DCD=0 %
- Integrity requirement
- IEC 61508 - High demand
- ΛDD
- 0
- Probability of a hazardous failure per hour (PFHD)
- 2,79 x 10-⁸
Standards and Regulations
- Electromagnetic compatibility
- Conformance with EMC directive
- Noise emission
- EN 61000-6-4
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Conformance
- CE-compliant, additionally EN 61326-1
- ATEX
- II 3 G Ex nA IIC T4 Gc X
- UL, USA/Canada
- UL 508 Listed
- UL, USA/Canada
- UL 61010 Listed
- UL, USA/Canada
- Class I, Div. 2, Groups A, B, C, D T4
- UL, USA/Canada
- Class I, Zone 2, Group IIC T4
- DNV GL-Temperature
- B
- DNV GL-Humidity
- B
- DNV GL-Vibration
- A
- DNV GL-EMC
- B
- DNV GL-Enclosure
- Required protection according to the Rules shall be provided upon installation on board
Power supply
- Nominal supply voltage
- 24 V DC
- Supply voltage range
- 19.2 V DC - 30 V DC (24 V DC -20%...+25%)
- Max. current consumption
- < 46 mA (24 V DC / 20 mA)
- Power dissipation
- < 1.1 W (24 V DC / 20 mA)
Other Categories
NanometersManometersFlowmetersSensorsAcceleration SensorsFiber Optic SensorsDetectorsUltrasonic SensorsTemperature & Humidity SensorsVibration SensorsLevel SensorsPressure SensorsProximity SensorsInductive SensorsMotion SensorsMagnetic Sensors GroupOptical SensorsCapacitive SensorsPhotoelectric SensorsPosition SensorsEncodersOther sensors and Accessories