Uninterruptible power supply - STEP-UPS/24DC/24DC/3 - 2868703
2868703
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
$313.09
1
Payment methods:
A total of 3 Parts In-Stock from 5 Distributors

Additional Information

Part Number
2868703
UPC
4046356519939
Country of Origin
PL
ETIM
Group Code : EG000037
Group Description : Data and telecommunication
Class Description : UPS
Class Code : EC000382
Version : 7

Input data

Input voltage
24 V DC
Nominal input voltage
24 V DC
Input voltage range
22.5 V DC - 29.5 V DC
Current consumption (charging process)
< 0.5 A (Charging (ICharge = max, IOut = 0))
Current consumption (maximum)
4.7 A
Current consumption (idle)
< 30 mA
Fixed backup threshold
< 22.5 V
Variable connect threshold
1 V / 1 s
Input fuse, integrated
7 A (slow-blow, internal)

Charging process

Quality check of battery
Yes, every time it is charged and cyclically once a month
Deep discharge protection
< 15 V DC

Standards

EMC requirements for noise immunity
EN 61000-6-1
EMC requirements for noise immunity
EN 61000-6-2
EMC requirements for noise emission
EN 61000-6-3
EMC requirements for noise emission
EN 61000-6-4
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)

Dimensions

Width
108 mm
Height
90 mm
Depth
61 mm
Installation distance right/left
0 mm / 0 mm
Installation distance top/bottom
0 mm / 0 mm

General output data

Efficiency
> 98 % (Mains operation, with charged energy storage)

Connection data, input

Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
6.5 mm
Screw thread
M3

Connection data, output

Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
6.5 mm
Screw thread
M3

Output data (24 V DC battery operation)

Nominal output voltage
24 V DC
Output voltage range (depends on the input voltage)
23 V DC - 26.5 V DC (UOut = UIn (t-₁))
Nominal output current (IN)
3 A (0 °C - 40 °C)

Output data (24 V DC mains operation)

Nominal output voltage
24 V DC
Output voltage range (depends on the input voltage)
22.5 V DC - 29.5 V DC (UOut = UIn - 0.3 V DC)
Nominal output current (IN)
3 A (0 °C - 40 °C)

Ambient conditions

Degree of protection
IP20
Ambient temperature (operation)
0 °C - 40 °C
Ambient temperature (storage/transport)
-20 °C - 45 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2

Connection data for signaling

Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
6.5 mm
Screw thread
M3

Conformance/approvals

UL approvals
UL Listed UL 508
UL approvals
UL/C-UL Recognized UL 60950-1

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
EN 61000-4-2
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Electromagnetic HF field
EN 61000-4-3
Frequency range
80 MHz - 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1 GHz - 2 GHz
Frequency range
2 GHz - 3 GHz
Comments
Criterion A
Fast transients (burst)
EN 61000-4-4
Input
2 kV (Test Level 3 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 4 - asymmetrical)
Surge voltage load (surge)
EN 61000-4-5
Input
1 kV (Test Level 2 - symmetrical)
Output
1 kV (Test Level 2 - symmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
Conducted interference
EN 61000-4-6
I/O/S
asymmetrical
Frequency range
0.15 MHz - 80 MHz
Voltage
10 V (Test Level 3)
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.