Input data

Number of inputs
1
Configurable/programmable
Yes
Voltage input signal
0 V - 10 V (via DIP switch)
Voltage input signal
2 V - 10 V (via DIP switch)
Voltage input signal
0 V - 5 V (via DIP switch)
Voltage input signal
1 V - 5 V (via DIP switch)
Voltage input signal
10 V - 0 V (via DIP switch)
Voltage input signal
10 V - 2 V (via DIP switch)
Voltage input signal
5 V - 0 V (via DIP switch)
Voltage input signal
5 V - 1 V (via DIP switch)
Voltage input signal
0 V - 12 V (can be set via software)
Current input signal
0 mA - 20 mA (via DIP switch)
Current input signal
4 mA - 20 mA (via DIP switch)
Current input signal
0 mA - 10 mA (via DIP switch)
Current input signal
2 mA - 10 mA (via DIP switch)
Current input signal
20 mA - 0 mA (via DIP switch)
Current input signal
20 mA - 4 mA (via DIP switch)
Current input signal
10 mA - 0 mA (via DIP switch)
Current input signal
10 mA - 2 mA (via DIP switch)
Current input signal
0 mA - 24 mA (can be set via software)
Max. input voltage
12 V
Max. input current
24 mA
Input resistance of voltage input
> 120 kΩ
Input resistance current input
approx. 50 Ω (+ 0.7 V for test diode)

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
6.2 mm
Height
109.81 mm
Depth
119.2 mm

Connection data

Connection method
Screw connection
Stripping length
10 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² - 1.5 mm² (with ferrule)
Conductor cross section solid
0.14 mm² - 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² - 2.5 mm²
Conductor cross section AWG
24 - 12 (flexible)
Torque
0.5 Nm - 0.6 Nm

Output data

Number of outputs
1
Configurable/programmable
Yes
Voltage output signal
0 V - 10 V (via DIP switch)
Voltage output signal
2 V - 10 V (via DIP switch)
Voltage output signal
0 V - 5 V (via DIP switch)
Voltage output signal
1 V - 5 V (via DIP switch)
Voltage output signal
0 V - 10.5 V (can be set via software)
Current output signal
0 mA - 20 mA (via DIP switch)
Current output signal
4 mA - 20 mA (via DIP switch)
Current output signal
0 mA - 10 mA (via DIP switch)
Current output signal
2 mA - 10 mA (via DIP switch)
Current output signal
0 mA - 21 mA (can be set via software)
Max. output voltage
approx. 12.3 V
Max. output current
24.6 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 600 Ω (at 20 mA)
Ripple
< 20 mVPP (at 600 Ω)

Ambient conditions

Ambient temperature (operation)
-40 °C - 70 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Permissible humidity (operation)
5 % - 95 % (non-condensing)
Degree of protection
IP20 (not assessed by UL)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
0.2 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
0.1 %
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
2.8 %

Switching output

Output name
Switching output
Number of outputs
1
Contact type
1 N/O contact
Minimum switching voltage
1 V
Maximum switching voltage
30 V DC
Min. switching current
100 µA
Max. switching current
100 mA (at 30 V)

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Standards/regulations
EN 61000-4-2
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Standards/regulations
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
UL, USA/Canada
Class I, Div. 2, Groups A, B, C, D T6
UL, USA/Canada
Class I, Zone 2, Group IIC T6
DNV GL-Temperature
B
DNV GL-Humidity
B
DNV GL-Vibration
A
DNV GL-EMC
A
DNV GL-Enclosure
Required protection according to the Rules shall be provided upon installation on board

Power supply

Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption
32 mA (24 V DC)
Typical current consumption
63 mA (12 V DC)
Power consumption