Additional Information
- Part Number
- 2903301
- UPC
- 4046356732567
- Country of Origin
- CN
- ETIM
- Group Code : EG000019
- Group Description : Relays
- Class Description : Switching relay
- Class Code : EC001437
- Version : 7
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 40 mm
- Height
- 96 mm
- Depth
- 90 mm
Connection data 2
- Connection name
- Contact side
- Connection method
- Screw connection
- Stripping length
- 8 mm
- Conductor cross section solid
- 0.5 mm² - 4 mm²
- Conductor cross-section solid (2 conductors with same cross section)
- 0.5 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.5 mm² - 4 mm²
- Conductor cross section flexible
- 0.5 mm² - 4 mm² (Ferrule with plastic sleeve)
- Conductor cross section flexible (2 conductors with same cross section)
- 0.5 mm² - 2.5 mm²
- Conductor cross section flexible (2 conductors with same cross section)
- 0.5 mm² - 1.5 mm² (TWIN ferrule with plastic sleeve)
- Conductor cross section AWG
- 20 - 10 (solid)
- Conductor cross section AWG
- 20 - 12 (flexible)
- Torque
- 0.5 Nm - 0.6 Nm
Connection data
- Connection name
- Input side
- Connection method
- Screw connection
- Stripping length
- 8 mm
- Conductor cross section solid
- 0.5 mm² - 4 mm²
- Conductor cross-section solid (2 conductors with same cross section)
- 0.5 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.5 mm² - 4 mm²
- Conductor cross section flexible
- 0.5 mm² - 4 mm² (Ferrule with plastic sleeve)
- Conductor cross section flexible (2 conductors with same cross section)
- 0.5 mm² - 2.5 mm²
- Conductor cross section flexible (2 conductors with same cross section)
- 0.5 mm² - 1.5 mm² (TWIN ferrule with plastic sleeve)
- Conductor cross section AWG
- 20 - 10 (solid)
- Conductor cross section AWG
- 20 - 12 (flexible)
- Torque
- 0.5 Nm - 0.6 Nm
Contact side
- Contact type
- 2 PDT
- Type of switch contact
- Single contact
- Contact material
- AgNi
- Maximum switching voltage
- 250 V AC/DC
- Minimum switching voltage
- 10 V (At 24 mA)
- Min. switching current
- 10 mA (at 24 V)
- Maximum inrush current
- 30 A (20 ms, N/O contacts)
- Limiting continuous current
- 7 A (see diagram)
- Interrupting rating (ohmic load) max.
- 168 W (at 24 V DC)
- Interrupting rating (ohmic load) max.
- 124 W (at 48 V DC)
- Interrupting rating (ohmic load) max.
- 108 W (at 60 V DC)
- Interrupting rating (ohmic load) max.
- 52 W (at 110 V DC)
- Interrupting rating (ohmic load) max.
- 48 W (at 220 V DC)
- Interrupting rating (ohmic load) max.
- 1750 VA (for 250 V AC)
- Switching capacity
- 2 A (at 24 V, DC13)
- Switching capacity
- 0.22 A (at 120 V, DC13)
- Switching capacity
- 0.11 A (at 250 V, DC13)
- Switching capacity
- 3 A (at 24 V, AC15)
- Switching capacity
- 3 A (at 120 V, AC15)
- Switching capacity
- 1.5 A (at 240 V, AC15)
Ambient conditions
- Ambient temperature (operation)
- -40 °C - 50 °C
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
- Degree of protection
- IP20 (Relay base)
- Degree of protection
- RT I (Relay)
Environmental Product Compliance
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Coil side
- Nominal input voltage UN
- 230 V AC
- Input voltage range in reference to UN
- see diagram
- Mains frequency
- 50/60 Hz
- Typical input current at UN
- 13 mA
- Typical response time
- 5 ms - 15 ms
- Typical release time range
- 5 ms - 20 ms
- Coil voltage
- 230 V AC
- Protective circuit
- Varistor
- Operating voltage display
- Yellow LED
Standards and Regulations
- Standards/regulations
- DIN EN 50178
- Rated insulation voltage
- 250 V AC
- Rated surge voltage
- 4 kV
- Insulation
- Basic insulation
- Pollution degree
- 2
- Overvoltage category
- III