Additional Information

Part Number
2903806
UPC
4046356768849
Country of Origin
DE

Function

Web-based management
yes

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
72 mm
Height
90 mm
Depth
62 mm

Digital inputs

Description of the input
Digital input
Number of inputs
4
Switching level "0" signal
0 V AC - 50 V AC
Switching level "1" signal
90 V AC - 250 V AC

Ambient conditions

Ambient temperature (operation)
-25 °C - 70 °C (SMS mode only, note the derating information in the technical documentation for data connection)
Ambient temperature (storage/transport)
-40 °C - 85 °C
Permissible humidity (operation)
0 % - 95 %
Altitude
2000 m
Degree of protection
IP20

Conformance/approvals

Designation
CE
Identification
CE-compliant
Designation
FCC
Additional text
Part 15.107(a), 15.109(a)
Designation
ATEX
Identification
II 3 G Ex nA nC IIC T4 Gc X
Additional text
Please follow the special installation instructions in the documentation!
Designation
Corrosive gas test
Identification
ISA-S71.04-1985 G3 Harsh Group A

Environmental Product Compliance

REACh SVHC
Cadmium oxide 1306-19-0
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Wireless interface

Interface description
GSM / GPRS
Frequency
850 MHz (2 W (EGSM))
Frequency
900 MHz (2 W (EGSM))
Frequency
1800 MHz (1 W (EGSM))
Frequency
1900 MHz (1 W (EGSM))
GPRS
Multislot Class 10

Digital outputs

Output name
Relay output
Number of outputs
4
Contact type
N/O contact
Minimum switching voltage
5 V
Maximum switching voltage
125 V DC
Maximum switching voltage
250 V AC
Limiting continuous current
5 A
Switching capacity
750 VA
Electrical service life
150000 cycles (5 A / 30 V DC)
Electrical service life
150000 cycles (3 A / 120 V AC)
Electrical service life
30000 cycles (5 A / 250 V AC)

Interfaces

Interface 1
USB 2.0
Connection method
Mini-USB type B, 5-pos.
Transmission length
≤ 3 m (only for configuration and diagnostics)

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Standards/regulations
EN 61000-4-2
Contact discharge
± 6 kV
Indirect discharge
± 6 kV
Standards/regulations
EN 61000-4-3
Frequency range
26 MHz - 6 GHz
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
EN 61000-4-5
Signal
± 1 kV (Data line, asymmetrical)
Standards/regulations
EN 61000-4-6
Frequency range
0.15 MHz - 80 MHz
Conducted noise emission
Class B, area of application: Industry and residential
Standards/regulations
EN 61000-4-11
Standards/regulations
EN 50360
Standards/regulations
EN 50121-4

Power supply

Supply voltage range
93 V AC - 250 V AC (47.5 Hz - 63 Hz)
Max. current consumption
25 mA
Typical current consumption
15 mA (230 V AC)
Conductor cross section flexible max.
2.50 mm²
Conductor cross section flexible min.
0.20 mm²
Conductor cross section solid max.
2.50 mm²
Conductor cross section solid min.
0.20 mm²
Max. AWG conductor cross section, flexible
14
Min. AWG conductor cross section, flexible
24
Conductor cross section AWG max.
14
Conductor cross section AWG min.
24