Hybrid motor starter - ELR-H51-9-BUSBAR-COMPACT-SET - 2904337
2904337
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:

Input data

Input name
Control input right/left
Rated actuating voltage UC
24 V DC
Triggering voltage range
19.2 V DC - 30 V DC
Rated actuating current IC
5 mA
Switching threshold
9.6 V ('0' signal)
Switching threshold
19.2 V ('1' signal)
Switching level
< 5 V DC (For EMERGENCY STOP)
Typical turn-off time
< 30 ms

Connection data 2

Connection name
Load circuit
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 14
Torque
0.5 Nm - 0.6 Nm
Torque
5 lbf-in. - 7 lbf-in.

Connection data

Connection name
Control circuits
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 14
Torque
0.5 Nm - 0.6 Nm
Torque
5 lbf-in. - 7 lbf-in.

Insulation characteristics

Rated insulation voltage
500 V
Rated surge voltage
6 kV
Overvoltage category
III
Degree of pollution
2
Designation
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit
Insulation
Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
Insulation
Safe isolation (EN 50178) at operating voltage ≤ 300 V AC
Insulation
Basic isolation (IEC 60947-1) at operating voltage 300 - 500 V AC
Insulation
Safe isolation (EN 50178) at operating voltage 300 - 500 V AC
Designation
Isolation characteristics between the control input and control supply voltage to auxiliary circuit
Insulation
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Insulation
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC

Device supply

Rated control circuit supply voltage US
24 V DC
Control supply voltage range
19.2 V DC - 30 V DC
Rated control supply current IS
40 mA
Type of protection
Surge protection
Type of protection
Reverse polarity protection

Output data reply output

Output name
Acknowledge output
Note
Confirmation: floating change-over contact, signal contact
Contact type
1 PDT
Switching capacity according to IEC 60947-5-1
3 A (230 V, AC15)
Switching capacity according to IEC 60947-5-1
2 A (24 V, DC13)

Ambient conditions

Ambient temperature (operation)
-25 °C - 70 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C - 80 °C
Maximum altitude
≤ 2000 m
Degree of protection
IP20

UL data

SCCR
100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
SCCR
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA
6.5 A (480 V AC)
Group installation
20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
Group installation
30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Category code
NLDX / NRNT

Conformance/approvals

Designation
ATEX
Identification
II (2) G [Ex e] [Ex d] [Ex px]
Identification
II (2) D [Ex t] [Ex p]
Certificate
PTB 07 ATEX 3145
Designation
UL approval
Certificate
NLDX.E228652
Designation
Safety Integrity Level (SIL, IEC 61508)
Identification
≤ 3
Additional text
Safe shutdown
Identification
2
Additional text
Motor protection
Designation
Performance Level (ISO 13849)
Identification
e
Designation
Category (ISO 13849)
Identification
3

Output data load output

Output name
AC output
Rated operating voltage Ue
500 V AC
Operating voltage range
42 V AC - 550 V AC
Mains frequency
50/60 Hz
Load current range
1.5 A - 9 A
Trigger characteristic in acc. with IEC 60947-4-2
Class 10A
Cooling time
20 min. (for auto reset)
Leakage current
0 mA
Type of protection
Surge protection
Type of protection
Short-circuit protection

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Standards and Regulations

Designation
Standards/regulations
Standards/regulations
IEC 60947-1
Standards/regulations
EN 60947-4-2
Standards/regulations
IEC 61508
Standards/regulations
ISO 13849

Overspeed tripping

Operate threshold
> 45 A
Response time
< 2 s