Resistance/potiposition transducer - MINI MCR-2-POT-UI-PT-C - 2905006
2905006
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Input data

Potentiometer
100 Ω - 100 kΩ

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
6.2 mm
Height
109.81 mm
Depth
119.2 mm

Connection data

Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section solid
0.2 mm² - 2.5 mm² (with ferrule)
Conductor cross section solid
0.14 mm² - 2.5 mm² (without ferrule)
Conductor cross section flexible
0.14 mm² - 2.5 mm²
Conductor cross section AWG
24 - 12 (flexible)

Output data

Voltage output signal
1 V - 5 V (via DIP switch)
Voltage output signal
10 V - 0 V (via DIP switch)
Voltage output signal
0 V - 5 V (via DIP switch)
Voltage output signal
0 V - 10 V (via DIP switch)
Voltage output signal
0 V - 10.5 V (can be set via software)
Current output signal
0 mA - 20 mA (via DIP switch)
Current output signal
4 mA - 20 mA (via DIP switch)
Current output signal
20 mA - 0 mA (via DIP switch)
Current output signal
20 mA - 4 mA (via DIP switch)
Current output signal
0 mA - 21 mA (can be set via software)
Max. voltage output signal
approx. 12.3 V
Max. current output signal
24.6 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 600 Ω (at 20 mA)

Ambient conditions

Ambient temperature (operation)
-40 °C - 70 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Permissible humidity (operation)
5 % - 95 % (non-condensing)
Degree of protection
IP20 (not assessed by UL)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
0.2 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
0.4 %
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6

Standards and Regulations

Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Standards/regulations
EN 61000-4-2
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Standards/regulations
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
UL, USA/Canada
Class I, Div. 2, Groups A, B, C, D T5
UL, USA/Canada
Class I, Zone 2, Group IIC T5

Power supply

Supply voltage
24 V DC
Supply voltage
9.6 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Current consumption
33 mA (24 V DC)
Current consumption
68 mA (12 V DC)