Part Number
2905144
UPC
4046356920360
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Motor starter/Motor starter combination
Class Code : EC001037
Version : 7

Dimensions

Width
22.5 mm
Height
107.5 mm
Depth
114 mm

Connection data 2

Connection name
Load circuit
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 14

Connection data

Connection name
Control circuits
Connection method
Push-in connection
Stripping length
10 mm
Conductor cross section solid
0.2 mm² - 2.5 mm²
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section AWG
24 - 14

Insulation characteristics

Rated insulation voltage
550 V
Rated surge voltage
6 kV
Overvoltage category
III
Degree of pollution
2
Designation
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit
Insulation
Safe isolation (IEC 60947-1)
Designation
Isolation characteristics between the control input and control supply voltage to auxiliary circuit
Insulation
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Insulation
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC

Device supply

Rated control circuit supply voltage US
24 V DC
Control supply voltage range
19.2 V DC - 30 V DC
Rated control supply current IS
60 mA
Type of protection
Surge protection
Type of protection
Reverse polarity protection

Ambient conditions

Ambient temperature (operation)
-5 °C - 60 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C - 80 °C
Maximum altitude
≤ 2000 m
Degree of protection
IP20

UL data

SCCR
100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
SCCR
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA
0.6 A (480 V AC)
Group installation
20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
Group installation
30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded)
Category code
NLDX / NRNT

Conformance/approvals

Designation
UL approval
Certificate
NLDX.E228652
Certificate
NRNT.E172140

Output data load output

Output name
AC output
Rated operating voltage Ue
500 V AC
Operating voltage range
42 V AC - 550 V AC
Rated operating current Ie
0.6 A (AC-51)
Rated operating current Ie
0.6 A (AC-53a)
Mains frequency
50/60 Hz
Load current range
75 mA - 600 mA (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2
Class 10
Cooling time
20 min. (for auto reset)
Leakage current
0 mA
Type of protection
Surge protection

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Standards and Regulations

Designation
Standards/regulations
Standards/regulations
IEC 60947-1
Standards/regulations
EN 60947-4-2

Overspeed tripping

Operate threshold
> 10 A
Response time
< 0.5 s