- Nominal voltage UN
- 60 V AC (TN-S)
- Nominal frequency fN
- 50 Hz (60 Hz)
- Maximum continuous voltage UC
- 100 V AC
- Maximum continuous voltage UC
- 80 V DC
- Rated load current IL
- 26 A (30 °C)
- Residual current IPE
- ≤ 5 µA
- Nominal discharge current In (8/20) µs
- 2 kA
- Standby power consumption PC
- ≤ 75 mVA (at UREF)
- Standby power consumption PC
- ≤ 150 mVA (at UC)
- Reference test voltage UREF
- 66 V AC
- Combination wave UOC
- 4 kV
- Voltage protection level Up (L-N)
- ≤ 0.48 kV
- Voltage protection level Up (L-PE)
- ≤ 0.9 kV
- Voltage protection level Up (N-PE)
- ≤ 0.9 kV
- TOV behavior at UT (L-N)
- 120 V AC (5 s / withstand mode)
- TOV behavior at UT (L-N)
- 120 V AC (120 min / withstand mode)
- TOV behavior at UT (L-PE)
- 120 V AC (5 s / withstand mode)
- TOV behavior at UT (L-PE)
- 120 V AC (120 min / withstand mode)
- Response time tA (L-N)
- ≤ 25 ns
- Response time tA (L-PE)
- ≤ 100 ns
- Response time tA (N-PE)
- ≤ 100 ns
- Short-circuit current rating ISCCR
- 1.5 kA AC
- Short-circuit current rating ISCCR
- 1 kA DC
- Max. backup fuse with branch wiring
- not required
- Maximum backup fuse for through wiring
- 25 A (gG / B / C)