Type 3 surge protection plug 2906495
2906495
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price

Additional Information

Part Number
2906495
UPC
4055626082028

UL specifications

SPD Type
4CA
Maximum continuous operating voltage MCOV
255 V AC
Mode of protection
L-N
Mode of protection
L-G
Mode of protection
N-G
Power distribution system
Single phase
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-N)
1500 V
Measured limiting voltage MLV (L-G)
1200 V
Measured limiting voltage MLV (N-G)
1200 V
Nominal discharge current I<sub>n</sub>
3 kA

Dimensions

Height
44.8 mm
Width
17.5 mm
Depth
51.7 mm
Horizontal pitch
1 Div.

Ambient conditions

Degree of protection
IP20
Ambient temperature (operation)
-40 °C - 80 °C
Ambient temperature (storage/transport)
-40 °C - 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % - 95 %

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1

Protective circuit

Nominal voltage U<sub>N</sub>
230 V AC (TN-S)
Nominal voltage U<sub>N</sub>
230 V AC (TT - only in use with RCD)
Nominal frequency f<sub>N</sub>
50 Hz (60 Hz)
Maximum continuous voltage U<sub>C</sub>
255 V AC
Rated load current I<sub>L</sub>
16 A AC (at 63 °C)
Residual current I<sub>PE</sub>
≤ 5 µA
Nominal discharge current I<sub>n</sub> (8/20) µs
3 kA
Standby power consumption P<sub>C</sub>
≤ 350 mVA
Reference test voltage U<sub>REF</sub>
255 V AC
Combination wave U<sub>OC</sub>
6 kV
Voltage protection level U<sub>p</sub> (L-N)
≤ 1.25 kV
Voltage protection level U<sub>p</sub> (L-PE)
≤ 1.4 kV
Voltage protection level U<sub>p</sub> (N-PE)
≤ 1.4 kV
TOV behavior at U<sub>T</sub> (L-N)
440 V AC (5 s / withstand mode)
TOV behavior at U<sub>T</sub> (L-N)
440 V AC (120 min / withstand mode)
TOV behavior at U<sub>T</sub> (L-PE)
440 V AC (5 s / withstand mode)
TOV behavior at U<sub>T</sub> (L-PE)
440 V AC (120 min / withstand mode)
TOV behavior at U<sub>T</sub> (L-PE)
1455 V AC (200 ms / safe failure mode)
TOV behavior at U<sub>T</sub> (N-PE)
1200 V AC (200 ms / safe failure mode)
Response time t<sub>A</sub> (L-N)
≤ 25 ns
Response time t<sub>A</sub> (L-PE)
≤ 100 ns
Response time t<sub>A</sub> (N-PE)
≤ 100 ns
Short-circuit current rating I<sub>SCCR</sub>
1.5 kA AC
Max. backup fuse with branch wiring
16 A (B)
Maximum backup fuse for through wiring
16 A (B)

Standards and Regulations

Standards/specifications
EN 61643-11 2012