Input data
- Sensor types that can be used (TC)
- E, J, K, N as per IEC / EN 60584, L as per DIN 43760
- Temperature measuring range
- -250 °C - 1372 °C (Range depending on the sensor type)
- Input signal range
- -20 mV - 70 mV
- Measuring range span
- Min. 50 K for thermocouples, 3 mV for mV sources
- Voltage input signal
- -20 mV - 70 mV
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 12.5 mm
- Height
- 106.4 mm
- Depth
- 113.7 mm
Connection data
- Connection method
- Screw connection
- Stripping length
- 7 mm
- Screw thread
- M3
- Conductor cross section solid
- 0.2 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 14
- Torque
- 0.5 Nm - 0.6 Nm
Output data
- Signal output
- Current output
- Configurable/programmable
- Yes
- Current output signal
- 0 mA - 20 mA
- Current output signal
- 4 mA - 20 mA
- Load/output load current output
- max. 500 Ω
- Output ripple (current)
- < 50 µAPP
- Behavior in the event of a sensor error
- As per NE 43 or can be freely defined
- Configurable/programmable
- no
Ambient conditions
- Ambient temperature (operation)
- -20 °C - 60 °C (Any mounting position)
- Ambient temperature (storage/transport)
- -40 °C - 80 °C
- Maximum altitude
- ≤ 2000 m
- Permissible humidity (operation)
- 5 % - 95 % (non-condensing)
- Degree of protection
- IP20 (not assessed by UL)
- Noise immunity
- EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
EMC data
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Designation
- Fast transients (burst)
- Standards/regulations
- EN 61000-4-4
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
Standards and Regulations
- Electromagnetic compatibility
- Conformance with EMC directive
- Noise emission
- EN 61000-6-4
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Standards/regulations
- EN 61000-4-4
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Conformance
- CE-compliant, additionally EN 61326-1
- ATEX
- II 3G Ex nA ic IIC T4 Gc X
- UL, USA/Canada
- UL 508 Listed
- UL, USA/Canada
- UL 61010 Listed
- UL, USA/Canada
- Class I, Div. 2, Groups A, B, C, D T4
- UL, USA/Canada
- Class I, Zone 2, Group IIC T4
- GL
- C, EMC1
Power supply
- Nominal supply voltage
- 24 V DC
- Supply voltage range
- 19.2 V DC - 30 V DC (24 V DC -20%...+25%)
- Max. current consumption
- < 40 mA (24 V DC)
- Power dissipation
- < 1 W
Other Categories
NanometersManometersFlowmetersSensorsAcceleration SensorsFiber Optic SensorsDetectorsUltrasonic SensorsTemperature & Humidity SensorsVibration SensorsLevel SensorsPressure SensorsProximity SensorsInductive SensorsMotion SensorsMagnetic Sensors GroupOptical SensorsCapacitive SensorsPhotoelectric SensorsPosition SensorsEncodersOther sensors and Accessories