Solid-state relay module - PLC-OSC- 60DC/230AC/ 1 - 2967866
2967866
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:On Request
Best price:
108,88 zł

Additional Information

Part Number
2967866
UPC
4017918190552
Country of Origin
DE
ETIM
Group Code : EG000019
Group Description : Relays
Class Description : Optocoupler
Class Code : EC001504
Version : 7

Input data

Nominal input voltage UN
60 V DC
Input voltage range in reference to UN
0.8 - 1.2
Input voltage range
48 V DC - 72 V DC
Switching threshold "0" signal in reference to UN
≤ 0.3
Switching threshold "1" signal in reference to UN
≥ 0.8
Typical input current at UN
6 mA
Typical response time
10 ms (at UN)
Typical turn-off time
10 ms (at UN)
Operating voltage display
Yellow LED
Type of protection
Reverse polarity protection
Type of protection
Free-wheeling diode
Protective circuit/component
Polarity protection diode
Protective circuit/component
Damping diode
Transmission frequency
10 Hz
Power dissipation for nominal condition
0.36 W

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
6.2 mm
Height
80 mm
Depth
94 mm

Connection data 2

Connection name
Output side
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.14 mm² - 2.5 mm²
Conductor cross section flexible
0.14 mm² - 2.5 mm²
Conductor cross section AWG
26 - 14

Connection data

Connection name
Input side
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.14 mm² - 2.5 mm²
Conductor cross section flexible
0.14 mm² - 2.5 mm²
Conductor cross section AWG
26 - 14

Output data

Output voltage range
24 V AC - 253 V AC
Limiting continuous current
0.75 A (see derating curve)
Maximum inrush current
30 A (10 ms)
Min. load current
10 mA
Leakage current
< 1 mA (in off state)
Max. load value
4.5 A²s
Voltage drop at max. limiting continuous current
< 1 V
Output circuit
2-wire, floating
Type of protection
RCV circuit

Ambient conditions

Ambient temperature (operation)
-25 °C - 60 °C
Ambient temperature (storage/transport)
-25 °C - 70 °C

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Standards and Regulations

Connection in acc. with standard
CUL
Designation
Standards/regulations
Standards/regulations
IEC 60664
Standards/regulations
EN 50178
Insulation
Basic insulation
Pollution degree
2
Overvoltage category
III

CAD Models

traceparts
traceparts
Download