Safety relays 2981224
2981224
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 11 Parts In-Stock from 7 Distributors

Additional Information

Part Number
2981224
UPC
4017918949020
Country of Origin
DE

Input data

Rated control circuit supply voltage U<sub>S</sub>
24 V DC -15 % / +10 %
Rated control supply current I<sub>S</sub>
typ. 150 mA
Power consumption at U<sub>S</sub>
typ. 3.6 W
Inrush current
200 mA (at US)
Inrush current
< 40 mA (with Us/Ix to S10)
Inrush current
< 150 mA (with Us/Ix to S12)
Inrush current
> -60 mA (with Us/Ix to S22)
Inrush current
< 40 mA (with Us/Ix to S34)
Inrush current
< 40 mA (with Us/Ix to S35)
Current consumption
< 40 mA (with Us/Ix to S10)
Current consumption
< 40 mA (with Us/Ix to S12)
Current consumption
> -40 mA (with Us/Ix to S22)
Current consumption
0 mA (with Us/Ix to S34)
Current consumption
< 5 mA (with Us/Ix to S35)
Voltage at input/start and feedback circuit
24 V DC -15 % / +10 %
Typical response time
< 600 ms (automatic start)
Typical response time
< 70 ms (manual start)
Typ. starting time with U<sub>s</sub>
< 600 ms (when controlled via A1)
Typical release time
< 20 ms (when controlled via S11/S12 and S21/S22)
Typical release time
< 20 ms (when controlled via A1)
Concurrence input 1/2
Recovery time
< 1 s
Operating voltage display
1 x green LED
Status display
4 x green LEDs
Protective circuit
Surge protection Suppressor diode
Maximum switching frequency
0.5 Hz
Max. permissible overall conductor resistance
approx. 11 Ω (Input and start circuits at US)
Delay time
K3(t), K4(t) fixed depending on model
Filter time
1 ms (at A1 in the event of voltage dips at Us)
Filter time
max. 1.5 ms (at S10, S12; test pulse width)
Filter time
7.5 ms (at S10, S12; test pulse rate)
Filter time
Test pulse rate = 5 x Test pulse width

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
45 mm
Height
99 mm
Depth
114.5 mm

Connection data

Connection method
Screw connection
Pluggable
Yes
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3

Output data

Contact type
5 enabling current paths
Contact type
1 signaling current path
Contact material
AgSnO2
Maximum switching voltage
250 V AC/DC (Observe the load curve)
Minimum switching voltage
5 V AC/DC
Limiting continuous current
6 A (N/O contact, pay attention to the derating)
Limiting continuous current
6 A (N/C contact)
Maximum inrush current
20 A (Δt  100 ms, undelayed contacts)
Maximum inrush current
8 A (delayed contacts)
Inrush current, minimum
10 mA
Sq. Total current
55 A2 (observe derating)
Interrupting rating (ohmic load) max.
144 W (24 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.
288 W (48 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.
110 W (110 V DC, τ = 0 ms, delayed contacts: 77 W)
Interrupting rating (ohmic load) max.
88 W (220 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.
1500 VA (250 V AC, τ = 0 ms, delayed contacts: 2000 VA)
Maximum interrupting rating (inductive load)
42 W (24 V DC, τ = 40 ms, delayed contacts: 48 W)
Maximum interrupting rating (inductive load)
42 W (48 V DC, τ = 40 ms, delayed contacts: 40 W)
Maximum interrupting rating (inductive load)
42 W (110 V DC, τ = 40 ms, delayed contacts: 35 W)
Maximum interrupting rating (inductive load)
42 W (220 V DC, τ = 40 ms, delayed contacts: 33 W)
Switching capacity min.
50 mW
Mechanical service life
10x 106 cycles
Switching capacity (360/h cycles)
4 A (24 V DC)
Switching capacity (360/h cycles)
4 A (230 V AC)
Output fuse
10 A gL/gG (N/O contact)
Output fuse
6 A gL/gG (N/C contact)

Ambient conditions

Ambient temperature (operation)
-20 °C - 55 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C - 70 °C
Max. permissible relative humidity (operation)
75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)
75 % (on average, 85% infrequently, non-condensing)
Maximum altitude
≤ 2000 m (Above sea level)

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50
China RoHS
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Standards and Regulations

Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178/VDE 0160
Rated insulation voltage
250 V AC
Rated surge voltage/insulation
Basic insulation 4 kV:between all current paths and housingSafe isolation, reinforced insulation 6 kV:between 13/14, 23/24, 33/34, and the remaining current pathsbetween 13/14, 23/24, 33/34 among one another
Degree of pollution
2
Overvoltage category
III
Shock
15g
Vibration (operation)
10 Hz ...150 Hz, 2g
Conformance
CE-compliant

Safety-related characteristic data

Stop category
0
Stop category
1
Designation
IEC 61508 - High demand
Safety Integrity Level (SIL)
3 (for delayed contacts SIL 2)
Designation
IEC 61508 - Low demand
Safety Integrity Level (SIL)
3 (for delayed contacts SIL 2)
Designation
EN ISO 13849
Performance level (PL)
e (for delayed contacts PL d)
Category
4 (Undelayed contacts)
Category
3 (delayed contacts)
Designation
EN 62061
Safety Integrity Level Claim Limit (SIL CL)
3 (for delayed contacts SILCL 2)