Input data

Rated control circuit supply voltage U<sub>S</sub>
120 V AC/DC -20 % - +10 %
Rated control supply current I<sub>S</sub>
typ. 11 mA
Power consumption at U<sub>S</sub>
typ. 1.32 W
Inrush current
typ. 600 mA (Δt = 200 µs at Us)
Typ. starting time with U<sub>s</sub>
typ. 20 ms (when controlled via A1)
Typical release time
typ. 20 ms (when controlled via A1)
Recovery time
< 500 ms
Operating voltage display
1 x green LED
Protective circuit
Surge protection Varistor
Maximum switching frequency
0.5 Hz

Dimensions

Width
22.5 mm
Height
114.5 mm
Depth
112 mm

Connection data

Connection method
Spring-cage connection
Pluggable
Yes
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm

Output data

Contact type
5 enabling current paths
Contact type
2 confirmation current paths
Contact material
AgSnO2
Maximum switching voltage
230 V AC/DC (Observe the load curve)
Minimum switching voltage
5 V AC/DC
Limiting continuous current
6 A (N/O contact)
Limiting continuous current
3 A (N/C contact)
Maximum inrush current
6 A
Inrush current, minimum
10 mA
Sq. Total current
72 A2
Interrupting rating (ohmic load) max.
144 W (N/O contact, 24 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.
288 W (N/O contact, 48 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.
240 W (N/O contact, 60 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.
110 W (N/O contact, 110 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.
88 W (N/O contact, 220 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.
1380 VA (N/O contact, 230 V AC, τ = 0 ms)
Maximum interrupting rating (inductive load)
42 W (N/O contact, 24 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
42 W (N/O contact, 48 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
42 W (N/O contact, 60 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
42 W (N/O contact, 110 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
42 W (N/O contact, 220 V DC, τ = 40 ms)
Switching capacity
min. 50 mW
Mechanical service life
10x 106 cycles
Switching capacity (360/h cycles)
4 A (24 V (DC13))
Switching capacity (360/h cycles)
4 A (250 V (AC15))
Switching capacity according to IEC 60947-5-1
3 A (24 V (DC13))
Switching capacity according to IEC 60947-5-1
3 A (250 V (AC15))
Output fuse
10 A gL/gG (N/O contact)
Output fuse
4 A gL/gG (N/O contact, for low-demand applications)
Output fuse
6 A gL/gG (N/C contact)

Ambient conditions

Ambient temperature (operation)
-20 °C - 55 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Max. permissible relative humidity (operation)
75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)
75 % (on average, 85% infrequently, non-condensing)
Maximum altitude
≤ 2000 m (Above sea level)

Environmental Product Compliance

China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values

Standards and Regulations

Designation
Air clearances and creepage distances between the power circuits
Standards/regulations
DIN EN 50178
Rated insulation voltage
250 V
Rated insulation voltage
250 V
Rated surge voltage/insulation
4 kV basic insulation (4 kV safe isolation, reinforced insulation between A1/A2, 13/14, 23/24, 33/34 to 43/44, 53/54, 61/62, 71/72)
Degree of pollution
2
Overvoltage category
III
Shock
15g (In the event of stress caused by shock, contact reactions are possible for up to 2 ms.)
Vibration (operation)
10 Hz ...150 Hz, 2g (In the event of stress caused by vibration, contact reactions are possible for up to 1 ms.)
Conformance
CE-compliant

Safety-related characteristic data

Stop category
0
Designation
IEC 61508 - High demand
Safety Integrity Level (SIL)
1
Designation
IEC 61508 - Low demand
Safety Integrity Level (SIL)
1
Designation
EN ISO 13849
Performance level (PL)
c
Category
1
Safety Integrity Level Claim Limit (SIL CL)
1