ABB
1SAM340000R1005
MS132-1.0T Circuit Breaker for Primary Transformer Protection 0.63 ... 1.0 A
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
€27.84
1
Payment methods:
A total of 304 Parts In-Stock from 16 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€32.82
Additional Information
- Part Number
- 1SAM340000R1005
- UNSPSC
- 39121601
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Power circuit-breaker for trafo/generator/installation protection
- Class Code : EC000228
- Version : 7
Dimensions
- Product Net Width
- 45 mm
- Product Net Height
- 90 mm
- Product Net Depth / Length
- 86.75 mm
- Product Net Weight
- 0.215 kg
Technical
- Rated Service Short-Circuit Breaking Capacity (Ics)
- (230 V AC) 100 kA(400 V AC) 100 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu)
- (400 V AC) 100 kA
- Rated Instantaneous Short-Circuit Current Setting (Ii)
- 20 A
- Setting Range
- 0.63 ... 1.0 A
- Rated Operational Voltage
- Main Circuit 690 V AC
- Rated Operational Current (Ie)
- 1 A
- Rated Frequency (f)
- Main Circuit 50 HzMain Circuit 60 Hz
- Rated Impulse Withstand Voltage (Uimp)
- Main Circuit 6 kV
- Rated Insulation Voltage (Ui)
- 690 V
- Power Loss
- at Rated Operating Conditions per Pole 0.6 ... 1.5 W
- Number of Poles
- 3
- Conventional Free-air Thermal Current (Ith)
- Main Circuit 1 A
- Degree of Protection
- Housing IP20Main Circuit Terminals IP10
- Pollution Degree
- 3
- Electrical Durability
- 50000 cycle
- Mechanical Durability
- 100000 cycle
- Terminal Type
- Screw Terminals
- Connecting Capacity Main Circuit
- Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²Flexible 1/2x 0.75 ... 2.5 mm²Rigid 1/2x 1 ... 4 mm²
- Tightening Torque
- Main Circuit 0.8 ... 1.2 N·m
- Wire Stripping Length
- Main Circuit 9 mm
- Recommended Screw Driver
- M3.5Pozidriv 2
- Mounting Position
- 1 ... 6
- Mounting on DIN Rail
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Minimum Mounting Distance
- Electrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 9 mmOther Device Same Type, Vertical 150 mm
- Actuator Type
- Rotary Handle
- Contact Position Indication
- ON / OFF / TRIP
- Standards
- IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1
Classifications
- Object Classification Code
- F
- ETIM 4
- EC000228 - Power circuit-breaker for trafo/generator/installation prot.
- ETIM 5
- EC000228 - Power circuit-breaker for trafo/generator/installation prot.
- EClass
- V11.0 : 27370409
- IDEA Granular Category Code (IGCC)
- 4864 >> Enclosed 3 Pole Circuit Breakers
- E-Number (Finland)
- 3707269
Environmental
- Ambient Air Temperature
- Around the Enclosure 0 ... +40 °COperation -25 ... +70 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C
- Ambient Air Temperature Compensation
- Yes
- Maximum Operating Altitude Permissible
- 2000 m
- Resistance to Shock acc. to IEC 60068-2-27
- 11 ms Pulse 25g
- Resistance to Vibrations acc. to IEC 60068-2-6
- 5g / 3 ... 150 Hz
- RoHS Status
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Technical UL/CSA
- Short-Circuit Current Rating (SCCR)
- Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
- Maximum Operating Voltage UL/CSA
- Main Circuit 600 V AC
- Full Load Amps Motor Use
- (120 V AC) Single Phase 1 A(220 ... 240 V AC) Single Phase 1 A
- Locked Rotor Amps
- (120 V AC) Single Phase 6 A(220 ... 240 V AC) Single Phase 6 A
- Connecting Capacity Main Circuit UL/CSA
- Flexible 1/2x 16-12 AWGStranded 1/2x 16-12 AWG
- Tightening Torque UL/CSA
- Main Circuit 10 ... 12 in·lb
Ordering
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85362010