- Rated Operational Current AC-21A (Ie)
- (380 ... 415 V) 1600 A(500 V) 1600 A(690 V) 1600 A
- Rated Operational Current AC-22A (Ie)
- (380 ... 415 V) 1600 A(500 V) 1600 A(690 V) 1600 A
- Rated Operational Current AC-23A (Ie)
- (380 ... 415 V) 1600 A(500 V) 1600 A(690 V) 1600 A
- Rated Operational Current AC-31B (Ie)
- (380 ... 415 V) 1600 A
- Rated Operational Current AC-33B (Ie)
- (380 ... 415 V) 1000 A
- Rated Operational Power AC-23A (Pe)
- (380 ... 415 V) 710 kW(500 V) 900 kW(690 V) 1200 kW
- Conventional Free-air Thermal Current (Ith)
- Θ = 40 °C 1600 A
- Rated Impulse Withstand Voltage (Uimp)
- 12 kV
- Rated Insulation Voltage (Ui)
- 1000 V
- Rated Operational Voltage
- 1000 V
- Rated Short-time Withstand Current Low Voltage (Icw)
- for 1 s 50 kiloampere rms
- Motor Operational Voltage
- 24 V DC
- Power Loss
- 48 W
- Pollution Degree
- 3
- Handle Color
- Black
- Handle Type
- Direct mounted handle
- Switches Operating Mechanism
- Mechanism at the End of the Switch
- Distance Between Phases
- Standard
- Position of Line Terminals
- Top In - Bottom Out, Bottom In - Top Out
- Operating Mode
- Front operated
- Mounting Type
- Base mounting
- Number of Poles
- 3
- Degree of Protection
- Front IP20
- Transition Type
- Open