- Current Type
- AC
- Electrical Durability
- Ue =< 440 V 9000 cycleUe = 500 ... 690 V 9000 cycle20 cycles per hour
- Mechanical Durability
- 20000 cycle60 cycles per hour
- Number of Poles
- 3
- Power Loss
- 225 W
- Product Main Type
- SACE Emax
- Product Name
- Air Circuit Breaker
- Product Type
- Air Circuit Breaker
- Rated Current (In)
- 2000 A
- Rated Voltage (Ur)
- 690 V
- Rated Impulse Withstand Voltage (Uimp)
- 12 kV
- Rated Insulation Voltage (Ui)
- 1000 V
- Rated Operational Current (Ie)
- 2000 A
- Rated Operational Voltage
- 690 V AC
- Rated Service Short-Circuit Breaking Capacity (Ics)
- (220 V AC) 75 kA(230 V AC) 75 kA(380 V AC) 75 kA(400 V AC) 75 kA(415 V AC) 75 kA(440 V AC) 75 kA(500 V AC) 75 kA(660 V AC) 75 kA(690 V AC) 75 kA
- Rated Short-time Withstand Current Low Voltage (Icw)
- for 1 s 75 kAfor 3 s 65 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu)
- (220 V AC) 75 kA(230 V AC) 75 kA(380 V AC) 75 kA(400 V AC) 75 kA(415 V AC) 75 kA(440 V AC) 75 kA(500 V AC) 75 kA(660 V AC) 75 kA(690 V AC) 75 kA
- Rated Uninterrupted Current (Iu)
- 2000 A
- Release
- PR122/P-LSI
- Release Type
- EL
- Short-Circuit Performance Level
- S
- Standards
- IEC
- Sub-type
- E3
- Terminal Connection Type
- Withdrawable Circuit-Breakers
- Version
- W