ABB
1SFL447001R1411
AF140-30-11-14 Contactor
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
$695.25
1
Payment methods:
A total of 302 Parts In-Stock from 12 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€182.02
Additional Information
- Part Number
- 1SFL447001R1411
- UNSPSC
- 39121529
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Power contactor, AC switching
- Class Code : EC000066
- Version : 7
Dimensions
- Product Net Width
- 90 mm
- Product Net Depth / Length
- 126 mm
- Product Net Height
- 150 mm
- Product Net Weight
- 1.55 kg
Technical
- Number of Main Contacts NO
- 3
- Number of Main Contacts NC
- 0
- Number of Auxiliary Contacts NO
- 1
- Number of Auxiliary Contacts NC
- 1
- Rated Operational Voltage
- Main Circuit 690 V
- Rated Frequency (f)
- Main Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (Ith)
- acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 200 A
- Rated Operational Current AC-1 (Ie)
- (690 V) 40 °C 200 A(690 V) 70 °C 160 A
- Rated Operational Current AC-3 (Ie)
- (415 V) 55 °C 140 A(440 V) 55 °C 140 A(500 V) 55 °C 130 A(690 V) 55 °C 80 A(380 / 400 V) 55 °C 140 A(220 / 230 / 240 V) 55 °C 140
- Rated Operational Current AC-3e (Ie)
- (415 V) 60 °C 140 A(440 V) 60 °C 140 A(500 V) 60 °C 130 A(690 V) 60 °C 80 A(380 / 400 V) 60 °C 140 A(220 / 230 / 240 V) 60 °C 140 A
- Rated Operational Power AC-3 (Pe)
- (415 V) 75 kW(440 V) 90 kW(500 V) 90 kW(690 V) 75 kW(380 / 400 V) 75 kW(220 / 230 / 240 V) 37 kW
- Rated Operational Power AC-3e (Pe)
- (415 V) 75 kW(440 V) 90 kW(500 V) 90 kW(690 V) 75 kW(380 / 400 V) 75 kW(220 / 230 / 240 V) 37 kW
- Rated Breaking Capacity AC-3
- 8 x Ie AC-3
- Rated Breaking Capacity AC-3e
- 8.5 x Ie AC-3e
- Rated Making Capacity AC-3
- 10 x Ie AC-3
- Rated Making Capacity AC-3e
- 12 x Ie AC-3e
- Short-Circuit Protective Devices
- gG Type Fuses 315 A
- Rated Short-time Withstand Current Low Voltage (Icw)
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
- Maximum Breaking Capacity
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A
- Maximum Electrical Switching Frequency
- (AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour
- Rated Operational Current DC-1 (Ie)
- (110 V) 2 Poles in Series, 40 °C 160 A(220 V) 3 Poles in Series, 40 °C 160 A
- Rated Operational Current DC-3 (Ie)
- (110 V) 2 Poles in Series, 40 °C 160 A(220 V) 3 Poles in Series, 40 °C 160 A
- Rated Operational Current DC-5 (Ie)
- (110 V) 2 Poles in Series, 40 °C 160 A(220 V) 3 Poles in Series, 40 °C 160 A
- Rated Insulation Voltage (Ui)
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
- Rated Impulse Withstand Voltage (Uimp)
- Main Circuit 8 kV
- Mechanical Durability
- 5 million
- Maximum Mechanical Switching Frequency
- 300 cycles per hour
- Coil Operating Limits
- (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
- Rated Control Circuit Voltage (Uc)
- 50 Hz 250 ... 500 V60 Hz 250 ... 500 VDC Operation 250 ... 500 V
- Coil Consumption
- Average Pull-in Value 50 Hz 260 V·AAverage Pull-in Value 60 Hz 260 V·AHolding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·AHolding at Max. Rated Control Circuit Voltage DC 4 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 205 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 205 V·APull-in at Max. Rated Control Circuit Voltage DC 230 W
- Operate Time
- Between Coil De-energization and NO Contact Opening 37 ... 47 msBetween Coil Energization and NO Contact Closing 25 ... 55 ms
- Connecting Capacity Main Circuit
- Flexible 2 x 10 ... 70 mm²Rigid Cu-Cable 2 x 10 ... 95 mm²
- Connecting Capacity Auxiliary Circuit
- Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
- Degree of Protection
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
- Terminal Type
- Double Clamp
Eco Transparency
- Environmental Product Declaration - EPD
- 1SFC100092D0201
Classifications
- Object Classification Code
- Q
- ETIM 4
- EC000066 - Magnet contactor, AC-switching
- ETIM 5
- EC000066 - Magnet contactor, AC-switching
- EClass
- V11.0 : 27371003
- IDEA Granular Category Code (IGCC)
- 4758 >> Iec Contactors
- E-Number (Finland)
- 3706195
- E-Number (Norway)
- 4117622
Environmental
- Ambient Air Temperature
- Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C
- Maximum Operating Altitude Permissible
- Without Derating 3000 m
- RoHS Status
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Circular Value
- ABB EcoSolutions
- Yes
- Circular Design Principles Recyclability Rate
- Design for Closing Resource Loops - Standard EN45555 - 87.8 %
- End of Life Instructions
- 1SFC100112M0001
- Group Waste to Landfill Target
- Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
- Improved Resource Efficiency for Customers
- Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
- Sustainable Material Content
- Recycled Metal - 37 %
Technical UL/CSA
- NEMA Size
- 4
- Continuous Current Rating NEMA
- 135 A
- Horsepower Rating NEMA
- (200 V AC) Three Phase 40 Hp(230 V AC) Three Phase 50 Hp(460 V AC) Three Phase 100 Hp(575 V AC) Three Phase 100 Hp
- Maximum Operating Voltage UL/CSA
- Main Circuit 600 V
- General Use Rating UL/CSA
- (600 V AC) 200 A
- Horsepower Rating UL/CSA
- (200 V AC) Three Phase 40 hp(208 V AC) Three Phase 40 hp(220 ... 240 V AC) Three Phase 50 hp(440 ... 480 V AC) Three Phase 100 hp(550 ... 600 V AC) Three Phase 125 hp
Ordering
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85364900