Littelfuse
601
1 / 1
Description
When a harmful condition is detected, the 601’s output relay is deactivated after the specified trip delay. The output relay reactivates after power line conditions return to an acceptable level for the programmed restart delay (RD2). Eleven (11) setpoints are viewable with the 3-digit LED display or from a networked device: low voltage high voltage voltage unbalance low frequency high frequency RS485 address trip delay for voltage/frequency faults trip delay for single-phase faults rapid-cycle timer (RD1) restart delay after all faults (RD2) type of restart after all faults (manual or automatic) Six (6) parameters are viewable while the motor is running: L1-L2 voltage L2-L3 voltage L1-L3 voltage average voltage voltage unbalance (%) voltage frequency (%) When used with the RS485MS-2W communications module, the 601 can communicate with most Modbus RTU master devices. Voltage conditions can be monitored and setpoints can be changed remotely using Solutions software, an RM-1000, RM-2000 or other device.- Part Number
- 601
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Specifications
- Input Voltage (V)
- 200 to 480VAC
- Maximum Input Power
- 5W
- Input AC Line Frequency (Hz)
- 50/60Hz
- Output Load Rating (VA)
- Pilot Duty: 480VA @ 240VAC; General purpose: 10A @ 240VAC
- Timing Accuracy (%)
- 5% ±1s
- Rapid Cycle Timer (s)
- 0 2 - 500s
- Restart Delay Range
- Restart Delay After All Faults: 2 - 500s
- Repeat Accuracy (%)
- Voltage: ±0.5%
- Trip Delay Range
- Voltage/Unbalance/Frequency Faults/Single-Phase Faults: 1 - 50s
- Overvoltage Reset Voltage (%)
- 97% of HV Setting
- Undervoltage Reset Voltage (%)
- 103% of LV Setting
- Voltage Unbalance Reset (%)
- UB Setting -1%
- Voltage Accuracy (%)
- ±1%
- Over/Under Frequency (%)
- Low: 35Hz - HF setting; High: LF setting - 75Hz
- Protection Class
- IP20 NEMA 1 (finger safe)
- Address
- A01-A99
- Termination Type
- Torque: 7in-lbs
- Mounting Method
- Surface mount (4 - #8 screws) or DIN rail mount
- Operating Temperature
- -20° to 70°C (-4° to 158°F)
- Storage Temperature (F/C)
- -40° to 80°C (-40° to 176°F)
- Humidity
- 10 - 95% non-condensing per IEC 68-2-3
- Dimensions
- 3.05 in H x 3.85 in W x 5.05 in D (77.5 x 97.8 x 128.3 mm)
- Weight (lbs/g)
- 1.2 lbs. (19.2 oz. 544.3 g)
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther