1 / 1
thumbnail

Description

When a harmful condition is detected, the 601’s output relay is deactivated after the specified trip delay. The output relay reactivates after power line conditions return to an acceptable level for the programmed restart delay (RD2). Eleven (11) setpoints are viewable with the 3-digit LED display or from a networked device: low voltage high voltage voltage unbalance low frequency high frequency RS485 address trip delay for voltage/frequency faults trip delay for single-phase faults rapid-cycle timer (RD1) restart delay after all faults (RD2) type of restart after all faults (manual or automatic) Six (6) parameters are viewable while the motor is running: L1-L2 voltage L2-L3 voltage L1-L3 voltage average voltage voltage unbalance (%) voltage frequency (%) When used with the RS485MS-2W communications module, the 601 can communicate with most Modbus RTU master devices. Voltage conditions can be monitored and setpoints can be changed remotely using Solutions software, an RM-1000, RM-2000 or other device.
Part Number
601
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Input Voltage (V)
200 to 480VAC
Maximum Input Power
5W
Input AC Line Frequency (Hz)
50/60Hz
Output Load Rating (VA)
Pilot Duty: 480VA @ 240VAC; General purpose: 10A @ 240VAC
Timing Accuracy (%)
5% ±1s
Rapid Cycle Timer (s)
0 2 - 500s
Restart Delay Range
Restart Delay After All Faults: 2 - 500s
Repeat Accuracy (%)
Voltage: ±0.5%
Trip Delay Range
Voltage/Unbalance/Frequency Faults/Single-Phase Faults: 1 - 50s
Overvoltage Reset Voltage (%)
97% of HV Setting
Undervoltage Reset Voltage (%)
103% of LV Setting
Voltage Unbalance Reset (%)
UB Setting -1%
Voltage Accuracy (%)
±1%
Over/Under Frequency (%)
Low: 35Hz - HF setting; High: LF setting - 75Hz
Protection Class
IP20 NEMA 1 (finger safe)
Address
A01-A99
Termination Type
Torque: 7in-lbs
Mounting Method
Surface mount (4 - #8 screws) or DIN rail mount
Operating Temperature
-20° to 70°C (-4° to 158°F)
Storage Temperature (F/C)
-40° to 80°C (-40° to 176°F)
Humidity
10 - 95% non-condensing per IEC 68-2-3
Dimensions
3.05 in H x 3.85 in W x 5.05 in D (77.5 x 97.8 x 128.3 mm)
Weight (lbs/g)
1.2 lbs. (19.2 oz. 544.3 g)

Documents

Data Sheet

Download