Type 2 surge protection plug - VAL-US 60 ST - 2800738
2800738
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price

Additional Information

Part Number
2800738
UPC
4046356643795
Country of Origin
DE
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Surge protection device for power supply systems
Class Code : EC000941
Version : 7

UL specifications

SPD Type
4CA
Maximum continuous operating voltage MCOV (L-N)
75 V AC
Maximum continuous operating voltage MCOV (L+) - (L-)
100 V DC
Nom. voltage
60 V AC
Nominal voltage
60 V DC
Mode of protection
L-N
Mode of protection
(L+) - (L-)
Power distribution system
Single phase
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-N)
630 V
Measured limiting voltage MLV (L+) - (L-)
810 V
Nominal discharge current In (L-N)
10 kA
Nominal discharge current In (L+) - (L-)
10 kA

Dimensions

Height
52.4 mm
Width
17.5 mm
Depth
55.3 mm
Horizontal pitch
1 Div.

Connection data

Connection method
VALVETRAB plug-in system

Ambient conditions

Degree of protection
IP20
Ambient temperature (operation)
-40 °C - 80 °C
Ambient temperature (storage/transport)
-40 °C - 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % - 95 %
Shock (operation)
25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (10 - 500 Hz / 2.5 h / X, Y, Z)

Protective circuit

Nominal voltage UN
60 V AC (TN)
Nominal voltage UN
60 V DC
Nominal voltage UN
-48 V DC (RRH)
Nominal frequency fN
60 Hz (50 Hz)
Maximum continuous voltage UC
75 V AC
Maximum continuous voltage UC
100 V DC
Residual current IPE
≤ 0.45 mA
Standby power consumption PC
≤ 35 mVA
Nominal discharge current In (8/20) µs
15 kA
Maximum discharge current Imax (8/20) µs
40 kA
Short-circuit current rating ISCCR
25 kA
Voltage protection level Up
≤ 0.55 kV
Residual voltage Ures
≤ 0.55 kV (at In)
Residual voltage Ures
≤ 0.425 kV (at 10 kA)
Residual voltage Ures
≤ 0.325 kV (at 5 kA)
Residual voltage Ures
≤ 0.275 kV (at 3 kA)
TOV behavior at UT
100 V AC (5 s / withstand mode)
Response time tA
≤ 25 ns
Max. backup fuse with branch wiring
125 A AC (gG)
Max. backup fuse with branch wiring
50 A DC (gG)

Standards and Regulations

Standards/regulations
IEC 61643-11 2011
Standards/regulations
EN 61643-11 2012