Surge protection device 2800807
2800807
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price

Additional Information

Part Number
2800807
UPC
4046356665254
Country of Origin
DE

Additional descriptions

Note
Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.

Dimensions

Height
91.1 mm
Width
17.7 mm
Depth
77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch
1 Div.

Connection data

Connection method
Screw connection
Screw thread
M3
Tightening torque
0.5 Nm
Stripping length
8 mm
Conductor cross section flexible
0.2 mm² - 2.5 mm²
Conductor cross section solid
0.2 mm² - 4 mm²
Conductor cross section AWG
24 - 12

Connection, equipotential bonding

Connection method
DIN rail NS35

Ambient conditions

Ambient temperature (operation)
-40 °C - 70 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Altitude
≤ 4000 m (amsl (above mean sea level))
Degree of protection
IP20

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1

Protective circuit

IEC test classification
C1
IEC test classification
C2
IEC test classification
C3
IEC test classification
D1
Nominal voltage U<sub>N</sub>
5 V DC
Maximum continuous voltage U<sub>C</sub>
6 V DC
Maximum continuous voltage U<sub>C</sub>
4 V AC
Rated current
700 mA (50 °C)
Operating effective current I<sub>C</sub> at U<sub>C</sub>
≤ 2 mA (in the signal circuit)
Residual current I<sub>PE</sub>
≤ 2 µA (per signal circuit)
Nominal discharge current I<sub>n</sub> (8/20) µs (line-line)
10 kA
Nominal discharge current I<sub>n</sub> (8/20) µs (line-earth)
10 kA
Pulse discharge current I<sub>imp</sub> (10/350) µs (line-earth)
2.5 kA
Total discharge current I<sub>total</sub> (8/20) µs
20 kA
Voltage protection level U<sub>p</sub> (line-line)
≤ 85 V (C1 - 1 kV/500 A)
Voltage protection level U<sub>p</sub> (line-line)
≤ 110 V (C2 - 10 kV / 5 kA)
Voltage protection level U<sub>p</sub> (line-line)
≤ 140 V (C2 - 10 kA)
Voltage protection level U<sub>p</sub> (line-line)
≤ 25 V (C3 - 25 A)
Voltage protection level U<sub>p</sub> (line-line)
≤ 25 V (C3 - 50 A)
Voltage protection level U<sub>p</sub> (line-earth)
≤ 600 V (C1 - 1 kV/500 A)
Voltage protection level U<sub>p</sub> (line-earth)
≤ 750 V (C2 - 10 kV / 5 kA)
Voltage protection level U<sub>p</sub> (line-earth)
≤ 800 V (C2 - 10 kA)
Voltage protection level U<sub>p</sub> (line-earth)
≤ 700 V (C3 - 25 A)
Voltage protection level U<sub>p</sub> (line-earth)
≤ 800 V (C3 - 100 A)
Voltage protection level U<sub>p</sub> static (line-line)
≤ 26 V (C1 - 1 kV/500 A)
Voltage protection level U<sub>p</sub> static (line-line)
≤ 70 V (C2 - 10 kV / 5 kA)
Voltage protection level U<sub>p</sub> static (line-line)
≤ 30 V (C2 - 10 kA)
Response time t<sub>A</sub> (line-line)
≤ 1 ns
Response time t<sub>A</sub> (line-earth)
≤ 100 ns
Input attenuation aE, sym.
typ. 0.3 dB (≤ 40 kHz/150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
typ. 300 kHz
Capacity (line-line)
typ. 7.5 nF
Resistance in series
1.2 Ω ±5 %
Surge protection fault message
Optical, multi-stage
Max. required back-up fuse
800 mA (FF)
Impulse durability (line-line)
C1 - 1 kV/500 A
Impulse durability (line-line)
C2 - 10 kV/5 kA
Impulse durability (line-line)
C2 - 10 kA
Impulse durability (line-line)
C3 - 50 A
Impulse durability (line-earth)
C1 - 1 kV/500 A
Impulse durability (line-earth)
C2 - 10 kV/5 kA
Impulse durability (line-earth)
C2 - 10 kA
Impulse durability (line-earth)
C3 - 100 A
Impulse durability (line-earth)
D1 - 2.5 kA
Pulse reset time (line-line)
≤ 10 ms
Pulse reset time (line-earth)
≤ 10 ms

Standards and Regulations

Standards/specifications
IEC 61643-21 2000 + A1:2008, modified
Standards/specifications
EN 61643-21 2001 + A1:2009
Standards/specifications
EN 61000-6-3 2007 + A1:2011
Standards/specifications
EN 61000-6-2 2005