Additional Information
- Part Number
- 2905025
- Country of Origin
- DE
- ETIM
- Group Code : EG000026
- Group Description : Sensors
- Class Description : Isolation amplifier
- Class Code : EC002653
- Version : 7
Input data
- Number of inputs
- 1
- Configurable/programmable
- Yes
- Voltage input signal
- 0 V - 10 V (via DIP switch)
- Voltage input signal
- 2 V - 10 V (via DIP switch)
- Voltage input signal
- 0 V - 5 V (via DIP switch)
- Voltage input signal
- 1 V - 5 V (via DIP switch)
- Voltage input signal
- 0 V - 12 V (can be set via software)
- Current input signal
- 0 mA - 20 mA (via DIP switch)
- Current input signal
- 4 mA - 20 mA (via DIP switch)
- Current input signal
- 0 mA - 10 mA (via DIP switch)
- Current input signal
- 20 mA - 0 mA (via DIP switch)
- Current input signal
- 0 mA - 24 mA (can be set via software)
- Max. input voltage
- 12 V
- Max. input current
- 24 mA
- Input resistance of voltage input
- > 120 kΩ
- Input resistance current input
- approx. 50 Ω (+ 0.7 V for test diode)
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 6.2 mm
- Height
- 109.81 mm
- Depth
- 119.2 mm
Connection data
- Connection method
- Screw connection
- Stripping length
- 10 mm
- Screw thread
- M3
- Conductor cross section solid
- 0.2 mm² - 1.5 mm² (with ferrule)
- Conductor cross section solid
- 0.14 mm² - 2.5 mm² (without ferrule)
- Conductor cross section flexible
- 0.14 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 12 (flexible)
- Torque
- 0.5 Nm - 0.6 Nm
Output data
- Number of outputs
- 2
- Voltage output signal
- 0 V - 10 V (via DIP switch)
- Voltage output signal
- 2 V - 10 V (via DIP switch)
- Voltage output signal
- 0 V - 5 V (via DIP switch)
- Voltage output signal
- 1 V - 5 V (via DIP switch)
- Voltage output signal
- 0 V - 10.5 V (can be set via software)
- Current output signal
- 0 mA - 20 mA (via DIP switch)
- Current output signal
- 4 mA - 20 mA (via DIP switch)
- Current output signal
- 0 mA - 10 mA (via DIP switch)
- Current output signal
- 20 mA - 0 mA (via DIP switch)
- Current output signal
- 0 mA - 21 mA (can be set via software)
- Max. output voltage
- approx. 12.3 V
- Max. output current
- 24.6 mA
- Short-circuit current
- ≤ 25 mA
- Load/output load voltage output
- ≥ 10 kΩ
- Load/output load current output
- ≤ 600 Ω (per channel)
- Ripple
- < 20 mVPP (at 600 Ω)
Ambient conditions
- Ambient temperature (operation)
- -40 °C - 70 °C
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
- Permissible humidity (operation)
- 5 % - 95 % (non-condensing)
- Degree of protection
- IP20 (not assessed by UL)
- Noise immunity
- EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
EMC data
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Typical deviation from the measuring range final value
- 0.2 %
- Designation
- Fast transients (burst)
- Standards/regulations
- EN 61000-4-4
- Typical deviation from the measuring range final value
- 0.1 %
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Typical deviation from the measuring range final value
- 2.8 %
Standards and Regulations
- Electromagnetic compatibility
- Conformance with EMC directive
- Noise emission
- EN 61000-6-4
- Standards/regulations
- EN 61000-4-2
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Standards/regulations
- EN 61000-4-4
- Standards/regulations
- EN 61000-4-5
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Electrical isolation
- Reinforced insulation in accordance with IEC 61010-1
- Conformance
- CE-compliant
- ATEX
- II 3 G Ex nA IIC T4 Gc X
- UL, USA/Canada
- UL 508 Listed
- UL, USA/Canada
- Class I, Div. 2, Groups A, B, C, D T6
- UL, USA/Canada
- Class I, Zone 2, Group IIC T6
- DNV GL-Temperature
- B
- DNV GL-Humidity
- B
- DNV GL-Vibration
- A
- DNV GL-EMC
- A
- DNV GL-Enclosure
- Required protection according to the Rules shall be provided upon installation on board
Power supply
- Nominal supply voltage
- 24 V DC
- Supply voltage range
- 9.6 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
- Typical current consumption
- 55 mA (24 V DC)
- Typical current consumption
- 110 mA (12 V DC)
- Power consumption
- ≤ 1.5 W (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
Other Categories
NanometersManometersFlowmetersSensorsAcceleration SensorsFiber Optic SensorsDetectorsUltrasonic SensorsTemperature & Humidity SensorsVibration SensorsLevel SensorsPressure SensorsProximity SensorsInductive SensorsMotion SensorsMagnetic Sensors GroupOptical SensorsCapacitive SensorsPhotoelectric SensorsPosition SensorsEncodersOther sensors and Accessories