Phoenix Contact
2905162
Hybrid motor starter - ELR H3-I-SC/500AC-06-IFS - 2905162
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
Send request for price
Additional Information
- Part Number
- 2905162
- UPC
- 4046356920292
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Motor starter/Motor starter combination
- Class Code : EC001037
- Version : 7
Dimensions
- Width
- 22.5 mm
- Height
- 107 mm
- Depth
- 114 mm
Connection data 2
- Connection name
- Load circuit
- Connection method
- Screw connection
- Stripping length
- 8 mm
- Screw thread
- M3
- Conductor cross section solid
- 0.2 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 14
- Torque
- 0.5 Nm - 0.6 Nm
- Torque
- 5 lbf-in. - 7 lbf-in.
Connection data
- Connection name
- Control circuits
- Connection method
- Screw connection
- Stripping length
- 8 mm
- Screw thread
- M3
- Conductor cross section solid
- 0.2 mm² - 2.5 mm²
- Conductor cross section flexible
- 0.2 mm² - 2.5 mm²
- Conductor cross section AWG
- 24 - 14
- Torque
- 0.5 Nm - 0.6 Nm
- Torque
- 5 lbf-in. - 7 lbf-in.
Insulation characteristics
- Rated insulation voltage
- 550 V
- Rated surge voltage
- 6 kV
- Overvoltage category
- III
- Degree of pollution
- 2
- Designation
- Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit
- Insulation
- Safe isolation (IEC 60947-1)
- Designation
- Isolation characteristics between the control input and control supply voltage to auxiliary circuit
- Insulation
- Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
- Insulation
- Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Device supply
- Rated control circuit supply voltage US
- 24 V DC
- Control supply voltage range
- 19.2 V DC - 30 V DC
- Rated control supply current IS
- 60 mA
- Type of protection
- Surge protection
- Type of protection
- Reverse polarity protection
Ambient conditions
- Ambient temperature (operation)
- -5 °C - 60 °C (observe derating)
- Ambient temperature (storage/transport)
- -40 °C - 80 °C
- Maximum altitude
- ≤ 2000 m
- Degree of protection
- IP20
UL data
- SCCR
- 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
- SCCR
- 5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
- FLA
- 0.6 A (480 V AC)
- Group installation
- 20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
- Group installation
- 30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded)
- Category code
- NLDX / NRNT
Conformance/approvals
- Designation
- UL approval
- Certificate
- NLDX.E228652
- Certificate
- NRNT.E172140
Output data load output
- Output name
- AC output
- Rated operating voltage Ue
- 500 V AC
- Operating voltage range
- 42 V AC - 550 V AC
- Rated operating current Ie
- 0.6 A (AC-51)
- Rated operating current Ie
- 0.6 A (AC-53a)
- Mains frequency
- 50/60 Hz
- Load current range
- 75 mA - 600 mA (see to derating)
- Trigger characteristic in acc. with IEC 60947-4-2
- Class 10
- Cooling time
- 20 min. (for auto reset)
- Leakage current
- 0 mA
- Type of protection
- Surge protection
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Standards and Regulations
- Designation
- Standards/regulations
- Standards/regulations
- IEC 60947-1
- Standards/regulations
- EN 60947-4-2
Overspeed tripping
- Operate threshold
- > 10 A
- Response time
- < 0.5 s