1 / 1
thumbnail

Description

Spring cage modular terminal block with integrated surge protection, for assembly on NS 35/7.5, voltage U<sub>N</sub> 12 V DC, terminal width: 6.2 mm, cover width: 2.2 mm
Country of Origin
DE
Part Number
2921310
Tariff Code
85363010
EAN
4046356279918
UPC
4046356279918
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Surge protection device for data networks/MCR-technology
Class Code : EC000943
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Dimensions

Height
100 mm
Width
6.2 mm
Depth
63.5 mm

Connection data

Connection method
Spring-cage connection
Connection method IN
Spring-cage
Connection method OUT
Spring-cage
Stripping length
8 mm
Conductor cross section flexible
0.5 mm² - 2.5 mm²
Conductor cross section solid
0.5 mm² - 4 mm²
Conductor cross section AWG
24 - 12

Ambient conditions

Ambient temperature (operation)
-40 °C - 85 °C
Degree of protection
IP20

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
China RoHS
No hazardous substances above threshold values

Protective circuit

IEC test classification
C1
IEC test classification
C3
VDE requirement class
C1
VDE requirement class
C3
Nominal voltage UN
12 V DC
Maximum continuous voltage UC
13 V DC
Maximum continuous voltage UC
9 V AC
Rated current
10 A (50 °C)
Operating effective current IC at UC
≤ 5 µA (DC)
Operating effective current IC at UC
≤ 20 µA (60 Hz)
Residual current IPE
≤ 10 µA (DC)
Residual current IPE
≤ 40 µA (60 Hz)
Nominal discharge current In (8/20) µs (line-earth)
700 A (per path)
Total discharge current Itotal (8/20) µs
1.4 kA
Nominal pulse current Ian (10/1000) µs (line-earth)
140 A (per path)
Output voltage limitation at 1 kV/µs (line-earth) spike
≤ 22 V
Output voltage limitation at 1 kV/µs (line-earth) static
≤ 22 V
Residual voltage at In (line-earth)
≤ 27 V
Residual voltage with Ian (10/1000) µs (line-earth)
≤ 22 V
Voltage protection level Up (line-earth)
≤ 25 V (C1 - 250 A)
Response time tA (line-earth)
≤ 1 ns
Input attenuation aE, asym.
typ. 0.3 dB (≤ 650 kHz / 50 Ω)
Input attenuation aE, asym.
typ. 0.1 dB (≤ 100 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (GND) in 50 Ohm system
typ. 1.7 MHz
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system
typ. 300 kHz
Capacity (line-earth)
≤ 5 nF
Surge protection fault message
none
Max. required back-up fuse
10 A (T)
Impulse durability (line-earth)
C1 - 500 V / 250 A
Impulse durability (line-earth)
C3 - 100 A
Alternating current carrying capacity (line-earth)
2 A - 5x 1 s

Standards and Regulations

Standards/regulations
IEC 61643-21
Standards/regulations
EN 61643-21
Standards/specifications
IEC 61643-21/A1 2008
Standards/specifications
EN 61643-21/A1 2009