Wago
2020-211/135-000
1 / 1
- Part Number
- 2020-211/135-000
- Tariff Code
- 85366990990
- UPC
- 4050821222118
- ETIM
- Group Code : EG000012
- Group Description : Terminal blocks
- Class Description : Single- and multi-pole terminal strip
- Class Code : EC001284
- Version : 7
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Ratings Per Iec/En
- Ratings per
- IEC/EN 61984
- Nominal voltage (III/3)
- 500 V
- Rated impulse voltage (III/3)
- 6 kV
- Rated current
- 13.5 A
- Legend (ratings)
- (III / 3) ≙ Overvoltage category III / Pollution degree 3
Environmental Requirements
- Processing temperature
- -35 … +85 °C
- Continuous operating temperature
- -60 … +105 °C
Plug-In Connection
- Contact type (pluggable connector)
- Female connector/socket
- Connector (connection type)
- For conductor
- Mismating protection
- No
- Plugging without loss of pin spacing
- No
- Strain relief
- Strain relief plate
Physical Data
- Width
- 39.2 mm / 1.543 inches
- Height
- 69 mm / 2.717 inches
- Depth
- 25 mm / 0.984 inches
- Module width
- 3.5 mm / 0.138 inches
Material Data
- Note (material data)
- <a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
- Color
- Gray
- Material group
- I
- Insulation material
- Polyamide (PA66)
- Flammability class per UL94
- V0
- Fire load
- 0.532 MJ
- Weight
- 31.349 g
Mechanical Data
- Variable coding
- Yes
- Marking level
- Side marking
- Anti-rotation protection
- Yes
Specifications
- Product Group Code
- 0018
Commercial Data
- Packaging type
- Box
- Country of origin
- DE
- GTIN
- 4050821222118
- Customs tariff number
- 85366990990
Notes
- Safety information
- According to EN 61984, pluggable connectors without current interrupting capacity must not be mated or unmated when live or under load.
- Safety information 2
- Notice: An appropriate end plate must be applied to the carrier terminal blocks after each female plug.
Ratings Per Csa
- Approvals per
- CSA 22.2 No 158
- Rated voltage CSA (Use Group B)
- 300 V
- Rated current CSA (Use Group B)
- 10 A
- Rated voltage CSA (Use Group C)
- 300 V
- Rated current CSA (Use Group C)
- 10 A
- Rated voltage CSA (Use Group D)
- 300 V
- Rated current CSA (Use Group D)
- 10 A
Connection 1
- Connection technology
- Push-in CAGE CLAMP®
- Actuation type
- Operating tool
- Connectable conductor materials
- Copper
- Nominal cross-section
- 1 mm²
- Solid conductor
- 0.14 … 1.5 mm² / 24 … 16 AWG
- Solid conductor; push-in termination
- 0.5 … 1.5 mm² / 20 … 16 AWG
- Fine-stranded conductor
- 0.14 … 1.5 mm² / 24 … 16 AWG
- Fine-stranded conductor; with insulated ferrule
- 0.14 … 0.75 mm² / 24 … 18 AWG
- Fine-stranded conductor; with ferrule; push-in termination
- 0.5 … 0.75 mm² / 20 … 18 AWG
- Note (conductor cross-section)
- Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
- Strip length
- 9 … 11 mm / 0.35 … 0.43 inches
- Pole number
- 11
- Wiring direction
- Front-entry wiring
Ratings Per Ul 1059
- Approvals per
- UL 1059
- Rated voltage UL (Use Group B)
- 300 V
- Rated current UL (Use Group B)
- 15 A
- Rated voltage UL (Use Group C)
- 300 V
- Rated current UL (Use Group C)
- 15 A
- Rated voltage UL (Use Group D)
- 300 V
- Rated current UL (Use Group D)
- 15 A