Wago
857-815
JUMPFLEX® signal conditioner; temperature; loop-powered RTD; configurable
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
€223.92
1
Payment methods:
A total of 14 Parts In-Stock from 13 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€164.23
Additional Information
- Part Number
- 857-815
- UPC
- 4055143475648
- Tariff Code
- 85437090300
- ETIM
- Group Code : EG000026
- Group Description : Sensors
- Class Description : Temperature transmitter
- Class Code : EC002919
- Version : 7
Output (Analog)
- Output signal type
- Current
- Output signal (current)
- 4 … 20 mA; 20 … 4 mA
- Load impedance (current output)
- See derating graphic
Signal Processing
- Step response (typ.)
- 1000 ms
Configuration
- Configuration options
- DIP switch
Environmental Requirements
- Ambient temperature (operation)
- -25 … +70 °C
- Ambient temperature (storage)
- -40 … +85 °C
- Temperature range of connection cable
- ≥ (Tambient + 10 K)
- Temperature range of connection cable (UL)
- 75 °C
- Relative humidity
- 5 … 95 % (no condensation permissible)
- Operating altitude (max.)
- 2000 m
Connection Data
- Connection technology
- Push-in CAGE CLAMP®
- Solid conductor
- 0.08 … 2.5 mm² / 28 … 14 AWG
- Fine-stranded conductor
- 0.34 … 2.5 mm² / 22 … 14 AWG
- Strip length
- 9 … 10 mm / 0.35 … 0.39 inches
Signaling And Communication
- Configuration options
- DIP switch
Input (Rtd Sensors)
- Sensor types (RTD)
- Pt100 || Pt200 || Pt500 || Pt1000
- Sensor connection
- 2-wire; 3-wire; 4-wire (switchable)
- Sensor power supply (RTD) max.
- ≤ 0.5 mA
- Temperature measurement range (RTD)
- -200 … 850°C
- Measurement span (RTD) min.
- 50 K
Supply
- Power supply type
- Loop-powered (via output)
- Supply voltage
- DC 8 … 30 V (Power is derived from the output circuit.)
- Power loss (max.) Pl (max.)
- 0.7 W
Physical Data
- Width
- 6 mm / 0.236 inches
- Height
- 94 mm / 3.701 inches
- Depth from upper-edge of DIN-rail
- 97.8 mm / 3.85 inches
Measurement Error
- Transmission error (typ.)
- ≤ 0.1 % at full measurement span
- Transmission error for the set measurement range
- ≤ ((40 K/set measurement range [K]) + 0.1) %
- Transmission error (under interference)
- ≤ 5 %
- Temperature coefficient
- ≤ 0.02 %/K
Material Data
- Fire load
- 0.013 MJ
- Weight
- 38.940 g
Input
- Input signal type
- Pt sensors || Resistance
Insulation Parameters(Ul)
- Overvoltage category
- II
- Pollution degree
- 2
- Insulation type (input/analog output)
- Reinforced insulation (safe isolation)
Standards And Specifications
- Conformity marking
- CE
- EMC immunity to interference
- EN 61000-6-2; EN 61326-1; EN 50121-3-2
- EMC emission of interference
- EN 61000-6-3; EN 61326-1; EN 50121-3-2
- Standards/specifications
- EN 61010-1 || EN 61373 || EN 50121-3-2
Mechanical Data
- Mounting type
- DIN-35 rail
Specifications
- Product Group Code
- 0006
Commercial Data
- Packaging type
- Bag
- Country of origin
- DE
- GTIN
- 4055143475648
- Customs tariff number
- 85437090300
Notes
- Note
- Use shielded signal lines!Only use shielded signal lines for analog input and output signals.Only then can you ensure that the accuracy and interference immunity specified for the device can be achieved, even in the presence of interference acting on the signal cable.
Test Voltage
- Test voltage (input/analog output)
- 3 kVAC; 50 … 60 Hz; 1 min
Input (Resistors)
- Input range (resistor)
- 0 … 1 kΩ; 0 … 4.5 kΩ
Other Categories
NanometersManometersFlowmetersSensorsAcceleration SensorsFiber Optic SensorsDetectorsUltrasonic SensorsTemperature & Humidity SensorsVibration SensorsLevel SensorsPressure SensorsProximity SensorsInductive SensorsMotion SensorsMagnetic Sensors GroupOptical SensorsCapacitive SensorsPhotoelectric SensorsPosition SensorsEncodersOther sensors and Accessories