Weidmuller

7940010250

URTAR
7940010250
7940010250
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€502.31

Additional Information

Part Number
7940010250

General Data

Accuracy
< 1 °C for 1 °C dissolution
Input/Output
Temperature converter
Linearity
± 0.1 % typ.
Long-term drift
0.1 % / 10.000 h
Power consumption
6 W @ 24 V DC
Rail
TS 35, TS 32
Repeat accuracy
± 0.05 % of signal range
Sampling rate
5x pro s
Step response time
320 ms (10...90 %),adjustable (250 ms...32 s)
Temperature coefficient
≤ 0.02 % / °C
Voltage supply
12...50 V DC

Approvals

Approvals
CE, CULUS
ROHS
Conform
UL File Number Search
E256486

Display

Type
4-character display
Display range
Depends on selected range
Display value
°C or °F
Resolution (display)
1 °C / °F or 0.1 °C / °F

Dimensions And Weights

Width
46 mm
Width (inches)
1.811 inch
Height
97 mm
Height (inches)
3.819 inch
Depth
120 mm
Depth (inches)
4.724 inch
Weight
493 g
Net weight
493 g

Connection Data

Type of connection
Screw connection
Clamping range, rated connection
1.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²

Alarm Output

Type
Alarm output with 2 NO contacts and suppressor circuit
Switching current
1 A @ 240 V AC / 30 V DC

Input

Type
2-/3-wire PT100 RTD
Input signal
2-/3-wire PT100. Ni120
Cable-length compensation
> 0.05 %
Line resistance in measuring circuit
30 Ω

Output (Analogue)

Load resistance current
≤ 900 Ω
Load resistance voltage
≥ 1 kΩ
Output current
0...22 mA
Output voltage
0...11 V
Transmit function
direct or inverted
Type (analogue output)
Voltage and current output (configurable)

Classifications

ETIM 6.0
EC000677
ETIM 7.0
EC000677
EClass 9.0
27-14-31-10
EClass 9.1
27-21-03-01
EClass 10.0
27-14-31-10
UNSPSC
30-21-18-01

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

EMC standards
DIN EN 61326
Impulse withstand voltage
4 kV (1.2/50 µs)
Insulation voltage
2 kV input / output / power supply
Rated voltage
300 Veff

Temperatures

Humidity
0...90 % (no condensation)
Operating temperature, max.
60 °C
Operating temperature, min.
0 °C
Storage temperature, max.
70 °C
Storage temperature, min.
-25 °C
Operating temperature
0 °C...60 °C
Storage temperature
-25 °C...70 °C

Ratings Iecex/Atex/Cul

Certificate no. (cULus)
E256486