ILX69-PBM
ILX69-PBM
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:

PROFIBUS DP Specifications

Specification
Description
Slaves
Maximum 125
Input/Output
Maximum 244 Bytes per Slave
Input Data
Maximum 5712 Bytes
Acyclic Data
DPV1
Status data
88 Bytes
Output data
Maximum 5760 Bytes
DPV1 services
Class 1 Alarm
DPV1 services
Class 2 Initiate/Read/Write/Data transport/Abort
Services
Global-Control, Slave-Diagnostic, Set-Parameter
Sync, Freeze Command
Supported
Baud rate
9.6 kBaud, 19.2 kBaud, 45.45 kBaud, 93.75 kBaud, 187.5 kBaud, 500 kBaud 1.5 MBaud, 3MBaud, 6 MBaud, 12 MBaud

Hardware Specification

Specification
Description
PROFIBUS Interface
RS-485, max. 12 Mbps, potential free, according EN 50170
Diagnostic Interface
10/100 Ethernet, RJ48
Power Supply
+5 V ±5 % / 570 mA
Max. Distance Rating
2 slots
Dimensions
Standard 1769 Single-slot module
Burst
EN 61000-4-4, 2 kV, 5 kHz
Surge
EN 61000-4-5, 2 kV common mode, 1 kVdifferential mode
ESD
EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect
Radiated/Conducted Immunity
EN 61000-4-3, 10 V/m, 30...1000 MHz, 80% AM, 1kHz sine wave
Radiated/Conducted Immunity
EN 61000-4-6, 10 V, 0,15...30 MHz
Radiated/Conducted Emission
EN 55011 Class A
Vibration/Shock
IEC 600068-2-6, 10-150 Hz, ± 0,75 mm, ± 1 g, 1Octave/min
Vibration/Shock
IEC 600068-2-27, 15 g, 11 ms
Operating Temperature
0°C to 60°C (32°F to 140°F)
Relative Humidity
5 to 95% (non-condensing)
PROFIBUS conformance
Certified