Specifications

Air flow monitoring
approx. 10% of total air flow
Benefits
["Early fire detection","Automatic extinguishing","Innovative extinguisher gas Novec 1230: eco-friendly, uncritical for IT components, non-conductive","19" rack mount with just 1 U","Tested by VdS Schadenverhtung GmbH","CAN-Bus Interface to CMC III monitoring system","Floating relay outputs (pre-alarm/main alarm/collective fault)"]
Width
4826 mm
Height
44 mm
Depth
660 mm
Display
Plain language display with 6 LEDs
Interfaces
4 x/3 x relay outputs for alarms and faults (terminals/RJ12 jacks), 1 x/1 x input for door contact switch (terminal/RJ12 jack), 2 x CAN connections for master-slave networking, 2 x connection (external alarm/manual triggering device), 1 x voltage output for DET-AC slave III (24 V DC max. 500 mA), 1 x USB, 2 x CAN bus interfaces to CMC III (max. 16 on PU/4 on PU Compact)
Material
Carbon steel
Note
The system has been designed exclusively for use in closed, non-walk-in enclosure systems with a maximum volume of 2.8 m.
Operating temperature range
10 C...40 C
Packaging unit
1 pc(s).
Rated operating voltage
100 V - 240 V, 1~, 50 Hz/60 Hz
Relative humidity (non-condensing)
0.96
Storage temperature range
-20 C...65 C
Storage temperature range, batteries
-15 C...40 C
Technical specifications
Extinguisher gas discharged by propellant gas cartridge, with integrated electrical trigger unit, Integrated extinguisher monitoring (indication of > 15% loss)
Uninterruptible mains electricity operation
approx. 4 hrs