Electrical data - AS-Interface specification
- AS-i Specification
- Safety-Slave
- AS-i Version
- V 2.1
- AS-i Profile
- S-0.B.F.E
- AS-i, IO-Code
- 0x0
- AS-i, ID-Code
- 0xB
- AS-i, ID-Code1
- 0xF
- AS-i, ID-Code2
- 0xE
- AS-i Input, Channel 1
- Data bits DI 0 / DI 1 = dynamic code transmission
- AS-i Input, Channel 2
- Data bits DI 2 / DI 3 = dynamic code transmission
- AS-i Outputs, DO 0 … DO 3
- No Function
- AS-i Parameter bits, P0 ... P3
- No function
- Note (AS-i Parameter bits)
- Set the parameter outputs to "1111" (0xF) | FID: periphery error
- AS-i Input module address
- 0
- Note (AS-i Input module address)
- Preset to address 0, can be changed through AS-interface bus master or hand-held programming device
Mechanical data - Dimensions
- Length of sensor
- 38.5 mm
- Width of sensor
- 40 mm
- Height of sensor
- 90 mm
Pin assignment
- PIN 1
- AS-i +
- PIN 2
- n.c.
- PIN 3
- AS-Interface -
- PIN 4
- n.c.
Ambient conditions - Insulation values
- Rated insulation voltage U
- 32 VDC
- Rated impulse withstand voltage U
- 0.8 kV
- Overvoltage category
- III
- Degree of pollution
- 3
Scope of delivery
- Scope of delivery
- Actuator must be ordered separately.
General data - Features
- Coding
- Yes
- Integral system diagnostics, status
- Yes
General data
- Standards
- EN IEC 62026-2 | EN ISO 13849-1 | EN IEC 60947-5-3 | EN IEC 61508
- Working principle
- Magnetic drive
- Installation conditions (mechanical)
- quasi-flush
- Enclosure material
- Glass-fibre, reinforced thermoplastic
- Gross weight
- 142 g
- Reaction time, maximum
- 100 ms
Safety classification
- Standards
- EN IEC 61508
- Performance Level, up to
- e
- Category
- 4
- PFH value
- 7.42 x 10⁻⁹ /h
- Note (PFH-value)
- up to max. 500,000 switching cycles/year
- Safety Integrity Level (SIL), suitable for applications in
- 3
- Mission time
- 20 Year(s)
Electrical data - AS Interface
- Rated operating voltage
- 18 ... 31.6 VDC (Protection against polarity reversal)
- AS-i Current consumption, maximum
- 50 mA
Ambient conditions
- Degree of protection
- IP67
- Ambient temperature
- -25 ... +60 °C
- Storage and transport temperature, minimum
- -25 °C
- Storage and transport temperature, maximum
- +70 °C
- Resistance to vibrations
- 10 … 55 Hz, amplitude 1 mm
- Restistance to shock
- 30 g / 11 ms
- Protection class
- II
Mechanical data - Connection technique
- Termination
- Connector plug M12, 4-pole, (A-coding)
- Connector position
- Right
Mechanical data - Switching distances according EN IEC 60947-5-3
- Assured switching distance "ON" S
- 8 mm
- Assured switching distance "OFF" S
- 18 mm
Mechanical data
- Active area
- front side
- Actuating element
- Magnet
- Note (Repeat accuracy R)
- Wiederholgenauigkeit R ≤ 0,1 x S
- Direction of motion
- Head-on to the active surface
Accessory
- Recommendation (actuator)
- BPS 16
Approvals - Standards
- Certificates
- TÜV | cULus | ASi-SaW
Status indication
- Note (LED switching conditions display)
- (1) LED yellow: Channel 1 / AS-i SaW Bit 0.1 | (2) LED green/red (AS-i duo LED): Supply voltage / communication error / slave address = 0 / periphery error detected | (3) LED yellow: Channel 2 / AS-i SaW Bit 2.3
CAD Models
Trace parts
DownloadOther Categories
NanometersManometersFlowmetersSensorsAcceleration SensorsFiber Optic SensorsDetectorsUltrasonic SensorsTemperature & Humidity SensorsVibration SensorsLevel SensorsPressure SensorsProximity SensorsInductive SensorsMotion SensorsMagnetic Sensors GroupOptical SensorsCapacitive SensorsPhotoelectric SensorsPosition SensorsEncodersOther sensors and Accessories