Schmersal

101182805

PROTECT-IE-11
101182805
101182805
101182805
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:

Electrical data - Relay outputs (auxiliary contacts)

Switching capacity, maximum
24 VDC
Switching capacity, maximum
0.1 A

Electrical data

Operating voltage
24 VDC -15 % / +20 %
Ripple voltage
10 %
Rated operating voltage
24 VDC
Rated AC voltage for controls at DC minimum
20.4 VDC
Rated control voltage at DC, maximum
28.8 VDC
Electrical power consumption
1.7 W
Input resistance at Ue
2,900 Ω
Contact resistance, maximum
0.1 Ω
Note (Contact resistance)
in new state
Drop-out delay in case of "emergency stop", maximum
20 ms
Pull-in delay at automatic start, maximum
20 ms

Mechanical data - Dimensions

Width
48 mm
Height
126 mm
Depth
61 mm

Ambient conditions - Insulation values

Rated impulse withstand voltage U
0.8 kV
Overvoltage category
III
Degree of pollution
2

Electrical data - Digital Output

Voltage, Utilisation category DC-12
24 VDC
Current, Utilisation category DC-12
0.1 A

General data - Features

Stop-Category
0
Electronic Fuse
Yes
Wire breakage detection
Yes
Cross-circuit detection
Yes
Automatic reset function
Yes
Earth connection detection
Yes
Integral system diagnostics, general
Yes
Number of auxiliary contacts
1
Number of LEDs
5
Number of normally closed (NC)
1
Number of normally open (NO)
1
Number of safety contacts
2

General data

Standards
EN IEC 62061 | EN ISO 13849-1 | EN IEC 60947-5-1 | EN IEC 60947-5-3 | EN IEC 60947-5-5 | EN IEC 61508 | EN IEC 60204-1 | EN IEC 60947-1
Climatic stress
EN 60068-2-78
Enclosure material
Glass-fibre reinforced thermoplastic, ventilated
Gross weight
140 g

Safety classification

Standards
EN IEC 60947-5-1 | EN IEC 61508
Performance Level, up to
d
Category
3
Diagnostic Coverage (DC) Level
60 %
PFH value
2.00 x 10⁻⁷ /h
Notice
for max. 36,500 switching cycles/year and max. 60% contact load
Safety Integrity Level (SIL), suitable for applications in
2
Mission time
20 Year(s)
Common Cause Failure (CCF), minimum
65

Other data

Note (applications)
Safety sensor | Guard system | Emergency-Stop button | Pull-wire emergency stop switches

Ambient conditions

Degree of protection of the enclosure
IP20
Degree of protection of the mounting space
IP20
Degree of protection of clips or terminals
IP20
Ambient temperature
-25 ... +55 °C
Storage and transport temperature, minimum
-40 °C
Storage and transport temperature, maximum
+85 °C
Resistance to vibrations
10...55 Hz, Amplitude 0.35 mm, ± 15 %
Restistance to shock
30 g / 11 ms

Mechanical data - Connection technique

Termination
Cage clamps
Terminal designations
IEC/EN 60947-1
Cable section, minimum
0.2 mm²
Cable section, maximum
2.5 mm²

Electrical data - Safe relay outputs

Voltage, Utilisation category DC-13
24 VDC
Current, Utilisation category DC-13
2 A
Switching capacity, minimum
10 VDC
Switching capacity, minimum
10 mA
Switching capacity, maximum
24 VAC
Switching capacity, maximum
2 A

Mechanical data

Mechanical life, minimum
10,000,000 Operations
Mounting
Snaps onto standard DIN rail to EN 60715

Specifications

Width
48 mm
Height
126 mm
Depth
61 mm

Approvals - Standards

Certificates
cULus

Electrical data - Electromagnetic compatibility (EMC)

EMC rating
EMC-Directive

Electrical data - Digital inputs

Input signal, HIGH Signal "1"
19 - 28,8 VDC
Input signal, LOW Signal "0"
0 - 1 VDC
Conduction resistance, maximum
40 Ω

Status indication

Indicated operating states
Position relay K2 | Position relay K1 | Position relay K3 | Position relay K3